User's Manual

- 2 -
TECHNICAL DATA
NOTES
1. Braided high pressure nitrogen tubing (P/N 87-120045-00X), is required to connect the XV Control System to the
System Valve Actuator (SVA) when the XV Control System is cylinder mounted.
2. Copper tubing shall be 1/4-inch O.D. x 0.031-inch wall high pressure tubing.
3. When Control System is cylinder mounted and two or more cylinders are being actuated, a minimum of 5 ft.
(1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used for actuation lines.
Table 1. Mechanical Cable Parameters for WHDR & IND Systems
XV Cable Line
Max. Cable
Length
Max. Corner
Pulleys
Max.
Detectors
Max. Tee
Pulleys
Detection and Manual Release-to-Trip Line 1 200 ft. (60.96 m) 50 40 *
Detection and Manual Release-to-Trip Line 2 200 ft. (60.96 m) 50 40 *
Pull-to-Trip Remote Manual Release Line 100 ft. (30.48 m) 30 - 1*
Mechanical Gas Valve Line 100 ft. (30.48 m) 30 - 1*
*Tee pulleys count as two Corner Pulleys. Maximum is from XV Control, through the pulley, to each device.
Table 2. Actuation Parameters for WHDR Wet Chemical Systems
Operating
Temperature
Range
Number of
Extinguishing
System Cylinders
Maximum Total Length
Copper Actuation Tubing
Minimum Total Length of Copper
Actuation Tubing
0
°F to 120°F
(-18
°C to 49°C)
1-12 106 ft. (32.30 m)
5 ft. (1.52 m)
13-20 91 ft. (27.73 m)
Table 3. Actuation Parameters for IND Industrial Dry Chemical and Open-Face Spray Booth Systems
Operating
Temperature
Range
Number of
Extinguishing
System Cylinders
Maximum Total Length
Copper Actuation Tubing
Minimum Total Length of Copper
Actuation Tubing
-40
°F to 120°F
(-40
°C to 49°C)
1-14 166 ft. (50.60 m)
5 ft. (1.52 m)
15-20 121 ft. (36.88 m)
Table 4. Actuation Parameters for IND Dry Chemical for Vehicle Spray Booths
Operating
Temperature
Range
Number of
Extinguishing
System Cylinders
Maximum Total Length
Copper Actuation Tubing
Minimum Total Length of Copper
Actuation Tubing
0
°F to 120°F
(-18
°C to 49°C)
1-8 200 ft. (60.96 m)
5 ft. (1.52 m)9-15 160 ft. (48.76 m)