February 2001
Table 5.2 Minimum Detector Sensitivity Setting
AREA - SQUARE METERS (FEET) LIGHT OBSCURATION - PERCENT PER METER (FOOT)
6096 (20,000) 0.076 (0.25)
5944 (19,500) 0.079 (0.26)
5791 (19,000) 0.085 (0.28)
5639 (18,500) 0.088 (0.29)
5486 (18,000) 0.091 (0.30)
5334 (17,500) 0.098 (0.32)
5182 (17,000) 0.101 (0.33)
5029 (16,500) 0.104 (0.34)
4877 (16,000) 0.110 (0.36)
4724 (15,500) 0.113 (0.37)
4572 (15,000) 0.116 (0.38)
4420 (14,500) 0.122 (0.40)
4267 (14,000) 0.128 (0.42)
4115 (13,500) 0.131 (0.43)
3962 (13,000) 0.137 (0.45)
3810 (12,500) 0.140 (0.46)
3658 (12,000) 0.146 (0.48)
3505 (11,500) 0.149 (0.49)
3353 (11,000) 0.155 (0.51)
3200 (10,500) 0.162 (0.53)
3048 (10,000) 0.165 (0.54)
2896 (9,500) 0.171 (0.56)
2743 (9,000) 0.177 (0.58)
2591 (8,500) 0.180 (0.59)
2438 (8,000) 0.186 (0.61)
2286 (7,500) 0.192 (0.63)
2134 (7,000) 0.198 (0.65)
1981 (6,500) 0.201 (0.66)
1829 (6,000) 0.207 (0.68)
1676 (5,500) 0.213 (0.70)
1524 (5,000) 0.220 (0.72)
1372 (4,500) 0.229 (0.75)
1219 (4,000) 0.235 (0.77)
1067 (3,500) 0.241 (0.79)
914 (3,000) 0.247 (0.81)
762 (2,500) 0.253 (0.83)
610 (2,000) 0.259 (0.85)
457 (1,500) 0.268 (0.88)
305 (1000) 0.274 (0.90)
152 (500) 0.284 (0.93)