Smoke Alarm User Manual
Installation, Operation and Maintenance Manual
Issue 1 Page 4-17
February 2001
4.7.4 Installation Checks
Prior to powering up the IIM for the first time ensure that the following procedures have been completed.
(1) The IIM is secured correctly.
(2) The IIM wiring is connected correctly.
(3) Each termination board located in the Detector has had its DIP switch set to the correct
address.
4.7.5
Installing Telephone Line to the Intelligent Interface Module
The following is a list of procedures for installation of a telephone line to the IIM.
(1) A standard telephone line should be installed adjacent to the IIM.
(2) Connect an RJ-11 cable from the telephone port on the IIM to the telephone line.
4.7.6 Software Configuration
For information on the software configuration reference should be made the LaserNET Version 3.0
Software Manual.
4.8 Programming
For system programming instructions reference should be made to the LaserNET Software Manual
Version 3.0.
4.9 Installation Method for the Elutriator
The Elutriator connects in series to the pipe network directly to the input, ¾ inch BSPT threaded hole
located on the top of the unit of the Detector.
NOTE
The orientation of the Elutriator. The side marked with an input connects to the pipe network.
The Elutriator comes with a set of four nylon washers.
If the Detector has been previously mounted, it must be removed and spacers added to the mounting
feet. Open the lid of the Detector by turning the two screws located on the bottom of the unit a quarter-
turn anti-clock wise. Once the lid is removed loosen the four mounting screws enough to slide the unit off
the wall.
Depending on the installation, rigid conduct fittings and Exhaust Port Adapter may need to be loosened or
disconnected. Slide one nylon washer over each of the four screws. Replace the Detector and tighten
the four mounting screws. Reassemble the Detector ensuring that all connections are correct.
Remove the Elutriator and attach it to the input (threaded hole located on the top) of the Detector. Rotate
the Elutriator (clockwise) by hand until the unit is secure. Using a 1-1/8 inch open-end spanner attached
to the bottom of the Elutriator, tighten another quarter-turn.
NOTE
Do not over-tighten.
To allow for greater serviceability it is recommended that a one foot section of smooth bore opaque pipe
be connected between the Elutriator and the pipe network.