User's Manual
3017FR DuPont Page 4
Material Safety Data Sheet
(ACCIDENTAL RELEASE MEASURES - Continued)
Accidental Release Measures
Material evaporates at atmospheric pressure (vaporizes).
Ventilate area, especially low places where heavy vapors
might collect. Remove open flames. Wear self-contained
breathing apparatus (SCBA) for large spills or when a
release occurs.
DuPont Fire Emergency Exposure Limits (FEEL) are established
to facilitate the safe release of a fire extinguishant into
spaces normally occupied by people to extinguish a fire or
prevent an explosion and specify airborne concentrations of
brief durations which should not result in permanent adverse
health effects or interfere with escape. For more
information on the applicability of FEEL’s, contact DuPont.
The DuPont Fire Emergency Exposure Limit (FEEL) for this
material is 20% v/v for up to 15 minutes with a 1 minute
not-to-exceed ceiling of 23% v/v.
----------------------------------------------------------------------
HANDLING AND STORAGE
----------------------------------------------------------------------
Handling (Personnel)
Avoid breathing high concentrations of vapor. Avoid contact
of liquid with eyes and prolonged skin exposure. Use with
sufficient ventilation to keep employee exposure below
recommended limits.
Storage
Clean, dry area. Do not heat above 51.7 deg C (125 deg F).
----------------------------------------------------------------------
EXPOSURE CONTROLS/PERSONAL PROTECTION
----------------------------------------------------------------------
Engineering Controls
Normal ventilation for routine manufacturing procedures is
generally adequate. Local exhaust should be used when large
amounts are released. Mechanical ventilation should be used
in low or enclosed places.
Personal Protective Equipment
Impervious gloves should be used when handling liquid.
Chemical splash goggles should be worn when handling liquid.
Under normal manufacturing conditions, no respiratory
protection is required when using this product. Self-
contained breathing apparatus (SCBA) is required if a large
spill or release occurs.
Exposure Guidelines