Specification

SPECIFICATIONS
STARTING METHOD: Rapid Start
LAMP CONNECTION: Series
INPUT VOLTAGE: 120-277VAC
±
10%
INPUT FREQUENCY: 50/60 Hz
POWER FACTOR: High
WARRANTY: 3 Years
2014 DOE Compliant
• Sound Rated: A
• Maximum Case Temperature: 194ºF, 90ºC
Meets FCC Part 18 (Class B) Consumer Limits
• Meets ANSI Standard C82.11-2005 and C62.41-2001
• OCV: 300V
• UL, cUL Listed (Class P, Type 1 Outdoor)
PRODUCT FEATURES
2x F34T12/F40T12 | 120-277V Input | High Power Factor | Rapid Start
DESCRIPTION
Page 1 of 2
Keystone Technologies 208 Progress Drive, Montgomeryville, PA 18936 Phone (800) 464-2680Fax (888) 966-0556 • www.keystoneballast.com
Specifications subject to change. Last revised on 3.6.15
ELECTRICAL SPECIFICATIONS
LAMP TYPE
NO. OF
LAMPS
INPUT
VOLTS
INPUT
WATTS
INPUT CURRENT
(AMPS)
POWER
FACTOR
CREST
FACTOR
BALLAST
FACTOR
BALLAST EFFICACY
FACTOR
MIN. START
TEMP
MAX THD
(%)
F40T12 2
120 72 0.62 0.98 1.70 0.85 1.18 32ºF/0ºC 10
277 70 0.26 0.98 1.70 0.85 1.21 32ºF/0ºC 10
F34T12* 2
120 62 0.55 0.98 1.70 0.85 1.37 32ºF/0ºC 10
277 61 0.23 0.98 1.70 0.85 1.39 32ºF/0ºC 10
F40T12
(25W Shoplight)
2
120 70 0.58 0.98 1.70 1.10 1.57 32ºF/0ºC 10
277 69 0.24 0.98 1.70 1.10 1.59 32ºF/0ºC 10
F30T12 2
120 58 0.48 0.98 1.70 0.93 1.60 32ºF/0ºC 10
277 56 0.20 0.98 1.70 0.93 1.66 32ºF/0ºC 10
WIRING DIAGRAM
BLACK
WHITE
YELLOW
YELLOW
RED
RED
BLUE
BLUE
LINE
LAMP
LAMP
BALLAST
HOT SPOT LOCATION
Actual tc point is noted on each ballast label.
YELLOW
YELLOW
RED
RED
BLUE
BLUE
BLACK
WHITE
6.7”
0.95”
LINE
KTEB-240-UV-TP-PIC
T12 ELECTRONIC FLUORESCENT
Version A1
* Primary Lamp Type.

Summary of content (2 pages)