Datasheet

05 | Keysight | N8700 Series System DC Power Supplies - Data Sheet
Performance Specications
1. Minimum voltage is guaranteed to maximum 0.2% of rated output voltage.
2. Minimum current is guaranteed to maximum 0.4% of rated output current.
3. 20 MHz
4. 5 Hz - 1 MHz
5. From no-load to full-load, constant input voltage. Maximum drop in remote sense.
6. For load voltage change equal to the unit voltage rating, constant input voltage
7. Single-phase and 3-Phase 208 V models: 170~265 VAC, constant load. 3-Phase 400 V models: 342~460 VAC, constant load.
8. The constant current programming readback and monitoring accuracy does not include the warm-up and load regulation thermal drift.
9. Time for output voltage to recover within 0.5% of its rated output for a load change 10 - 90% of rated output current, local sense.
N8731A N8732A N8733A N8734A N8735A N8736A
DC output ratings
Voltage
1
8 V 10 V 15 V 20 V 30 V 40 V
Current
2
400 A 330 A 220 A 165 A 110 A 85 A
Power 3200 W 3300 W 3300 W 3300 W 3300 W 3400 W
Output ripple and noise
CV
p-p
3
60 mV 60 mV 60 mV 60 mV 60 mV 60 mV
CV
rms
4
8 mV 8 mV 8 mV 8 mV 8 mV 8 mV
Load effect
CV load regulation
5
6.2 mV 6.5 mV 7.25 mV 8 mV 9.5 mV 11 mV
CC load regulation
6
85 mA 71 mA 49 mA 38 mA 27 mA 22 mA
Source effect
CV line regulation
7
2.8 mV 3 mV 3.5 mV 4 mV 5 mV 6 mV
CC line regulation
7
42 mA 35 mA 24 mA 18.5 mA 13 mA 10.5 mA
Programming accuracy
Voltage
1
0.05% + 4 mV 5 mV 7.5 mV 10 mV 15 mV 20 mV
Current
2, 8
0.1% +
800 mA 660 mA 440 mA 330 mA 220 mA 170 mA
Measurement accuracy
Voltage 0.1% + 8 mV 10 mV 15 mV 20 mV 30 mV 40 mV
Current
8
0.1% +
1200 mA 990 mA 660 mA 495 mA 330 mA 255 mA
Load transient recovery time
Time
9
<1 ms <1 ms <1 ms <1 ms <1 ms <1 ms