Datasheet

10 | Keysight | N8700 Series System DC Power Supplies - Data Sheet
Performance Specications (continued)
N8759A N8760A N8761A N8762A
DC output ratings
Voltage
1
100 V 150 V 300 V 600 V
Current
2
50 A 34 A 17 A 8.5 A
Power 5000 W 5100 W 5100 W 5100 W
Output ripple and noise
CV
p-p
3
100 mV 120 mV 300 mV 500 mV
CV
rms
4
15 mV 25 mV 60 mV 120 mV
Load effect
CV load regulation
5
20 mV 27.5 mV 50 mV 95 mV
CC load regulation
6
50 mA 34 mA 17 mA 8.5 mA
Source effect
CV line regulation
7
10 mV 15 mV 30 mV 60 mV
CC line regulation
7
25 mA 17 mA 8.5 mA 4.3 mA
Programming accuracy
Voltage
1
0.025% + 75 mV 112.5 mV 225 mV 450 mV
Current
2, 8
0.1% +
150 mA 102 mA 51 mA 25.5 mA
Measurement accuracy
Voltage 0.025% + 125 mV 187.5 mV 375 mV 750 mV
Current
8
0.1% +
150 mA 102 mA 51 mA 25.5 mA
Load transient recovery time
Time
9
<1 ms <2 ms <2 ms <2 ms
1. Minimum voltage is guaranteed to maximum 0.2% of rated output voltage.
2. Minimum current is guaranteed to maximum 0.4% of rated output current.
3. 20 MHz
4. 5 Hz - 1 MHz
5. From no-load to full-load, constant input voltage. Maximum drop in remote sense.
6. For load voltage change equal to the unit voltage rating, constant input voltage
7. Single-phase and 3-Phase 208 V models: 170~265 VAC, constant load. 3-Phase 400 V models: 342~460 VAC, constant load.
8. The constant current programming readback and monitoring accuracy does not include the warm-up and load regulation thermal drift.
9. Time for output voltage to recover within 0.5% of its rated output for a load change 10 - 90% of rated output current, local sense.