Datasheet

8
Series and parallel capability
Parallel operation
Up to 4 units can be connected in
master/slave mode
Series operation
Up to 2 units can be connected in
series
Output terminal isolation
6 V to 60 V units
No output terminal may be more than
±60 VDC from any other terminal or
chassis ground
80 V to 600 V units
No output terminal may be more than
±600 VDC from any other terminal or
chassis ground
Store-recall states
Volatile memory locations: 16
Analog programming
(of output voltage and current)
Input signal
Selectable;
0 to 5 V / 0 to 10 V full scale
Input impedance
Selectable;
0 to 5 kΩ / 0 to 10 kΩ full scale
Interface capabilities
GPIB
SCPI – 1993, IEEE 488.2 compliant
interface
USB 2.0
Requires Keysight I/O library version
L.01.01
10/100 LAN
Requires Keysight I/O library version
L.01.01
Web server
Built-in Web server requires Internet
Explorer 5+ or Netscape 6.2+
Environmental conditions
Environment
Indoor use, installation category II
(AC input), pollution degree 2
Operating temperature
0°C to 40°C @ 100% load
Storage temperature
–20°C to 70°C
Operating humidity
30% to 90% relative humidity
(no condensation)
Storage humidity
10% to 95% relative humidity
(no condensation)
Altitude
Up to 3000 meters.
Derate the output current by
2%/100 m above 2000 m.
Derate the maximum ambient
temperature by 1 °C/100 m
above 2000 m.
Regulatory compliance
EMC
European EMC directive 89/336/
EEC for Class A products
Australian C- Tick mark
This ISM device complies with
Canadian ICES-001.
Cet appareil ISM est conforme à
la norme NMB-001 du Canada.
Safety
European Low Voltage Directive
73/23/EEC
US and Canadian safety
standards
Any LEDs used in this product
are Class 1 as per IEC 825-1
Acoustic noise declaration
Emission directive:
Sound pressure Lp <70 dB(A),
At operator position,
*Normal operation,
*According to EN 27779 (Type
Test).
Schalldruckpegel Lp <70 dB(A)
*Am Arbeitsplatz, *Normaler
Betrieb, *Nach EN 27779
(Typprüfung).
AC input
Nominal input
100 – 240 VAC; 50/60 Hz
Input current 750 W
10.5 A @ 100 VAC nominal;
5 A @ 200 VAC nominal
Input current 1500 W
21 A @ 100 VAC nominal;
11 A @ 200 VAC nominal
Input range
85 – 265 VAC; 47 – 63 Hz.
Power factor
0.99 at nominal input and rated
output power
Efficiency
76% – 87% for 750 W units;
77% – 88% for 1500 W units
Inrush current
<25 A for 750 W units;
<50 A for 1500 W units
Dimensions
(excluding connectors, and handles)
Height 43.6 mm (1.72 in)
Width 422.8 mm (16.65
in)
Depth 432.8 mm (17.04
in)
Weight
750 W 7 Kg (15.4 lbs.)
1500 W 8.5 Kg (18.7 lbs.)
WARNING Shock Hazard
For models up to 60 VDC rated output, no point on the output shall be more than ± 60 VDC above or below chassis
ground.
For models greater than 60 VDC rated output, no point on the Positive output shall be more than ± 600 VDC above or
below chassis ground.
For models greater than 60 VDC rated output, no point on the Negative output shall be more than ± 400 VDC above or
below chassis ground.
Supplemental Characteristics for All Model Numbers