Instruction Manual
2-11
2-3 Connecting and Wiring to the N-R4 Series
Installation
2
Connecting the Power Supply
Connect the 24 VDC power supply to the power supply terminal block as shown in the figure.
Do not use a power supply other than 24 V DC. Otherwise, product failure
may occur.
Applicable terminals for power supply connection
The dimensions of crimp contacts used for wiring should be as follows:
Power supply
DC 24VDC
Twisted pair cable
* Although the figure shows the model "N-R2", the power supply
terminals are located in the same position on all models.
+10%
-
20%
Caution
Terminal Dimensions
Round Terminal a : 6.0 mm Max.
Y terminal a : 6.0 mm Max.
Item Description
Wire size AWG 14 to 22
Tightening torque 0.49 N·m (4.34 lbf·in)
Wire material Copper
Wire type Stranded wire
Electric wire
temperature rating
+60°C