Owner's manual

Table Of Contents
Chapter 6 PLC Link
112
6
A + 02 4
A + 03 5
A + 04 $0045
A + 05 $0052
A + 06 $0052
A + 07 $004F
A + 08 $0052
ID number
Number of digits
Specified by ASCII codes
(hexadecimal numbers)
"E"
"R"
"R"
"R"
"O"
The ID number of the BL series that read the data is stored in the A +02 ad-
dress. The number of data digits is stored in the A +03 address as binary data.
The read bar code data is stored in the A+04 to +258 addresses using the ASCII
codes (Hexadecimal numbers in two digits) by the digit. (
See the ASCII code
table on p134.
)
If a read error occurs, the “ERROR” code is stored in the corresponding area.
(The read error code can be easily changed according to the BL series’ setting.)
If the buffer overflow error occurs with the BL series, the “OVER” code is stored
in the corresponding area.
Note: These data areas accept up to 255 digits. However, the BL series can read
only 32 digits. Therefore, all of the areas for 255 digits are not used for the N-400.
Only the areas corresponding to the number of the data digits are used.
Example: When the BL series with ID No. 12 reads bar code data as “KE12”:
Example: When a read error (ERROR) occurs in the BL series with ID No. 4:
A +02 to +258
Data (ID number, number of digits, data) memory area
A+02 ID number (1 to 31)
A+03 Number of digits of bar code data (1 to 255)
A+04 1st digit of read data
A+05 2nd digit of read data
::
A+258 255th digit of read data
A + 02 12
A + 03 4
A + 04 $004B
A + 05 $0045
A + 06 $0031
A + 07 $0032
ID number
Number of digits
Specified by ASCII codes
(hexadecimal numbers)
"K"
"E"
"E"
"2"