Owner manual
5
LS-Navigator-M-NO5-E
5-26
5-10 Setting the Measurement Conditions for the Program
1 
Click on the [Settings list] tab in the 
program setting area.
A list of the set parameters appears in the 
[Settings list] window.
2 
Copy the settings to clipboard. Paste the 
settings in another application, such as 
Excel.
Reference
The parameters that have been changed from their 
default values are displayed in blue.
Settings list
Analog voltage is output for the measurement value.
For standard value mode: When the limit mode is 
standard value, the standard value is represented by 0 
V, and the output voltage is greater or smaller 
depending on the deviation. Select one of the following 
values from the pull-down menu.
Valid values:
1, 2, 5, 10, 20, 50, 100, 200, 500, 1000, 2000, 5000, 
10000 µm/V
Threshold m
ode: When the limit mode is threshold 
mode, set the measurement valu
es that you want to 
output at +10 V and -10 V. These values determine the 
scaling for the output.
Set the measurement values so that the absolute 
value of their difference satisfies the conditions of the 
following formula.
Absolute value of { (Measurement value for +10 V) - 
(Measurement value f
or -10V) }  X
The
 value for X changes depending on the minimum 
display unit setting.
The following chart indicates the relationship between 
X and the minimum display unit.
For more details, see the “Analog Output Settings” 
section in the “User’s Manual” for each controller.
Set the same values for [Units] and [Minimum display 
unit] in the settings f
or the controller and LS-Navi
gator. 
(Refer to  Page 5-5.)
Minimum display unit (mm) X (mm)
0.00001, 0.00002, 0.00005 0.02
0.0001, 0.0002 0.2
0.001, 0.01, 0.1 2
0.01, 0.02, 0.05 20
0.1, 0.2 200
1 2000
>_
Copies the output settings from OUT1 or 
OUT2 and pastes them into OUT1 or OUT2.
The entered value is added to or subtracted from the measurement 
value.
When an offset value is set while using the auto zero function, the 
offset appears on the display momentarily.
Valid range:
With the defaults, the range is -99.99999 to 99.99999 mm.
Reference
The offset value changes according to the units and the minimum 
display unit setting.
For more details, see the sections “Display Unit” and “Minimum 
Display Unit” in the “User’s Manual” for each controller.
2
1










