User Manual
12
GT2-70-M-E
■
Calibration setting mode
You can set the following functions in the calibration setting mode.
●
How to enter the calibration setting mode
Enter the calibration setting mode by the following procedure.
•
In the main display, press the [MODE] button and the right Arrow 
button at the same time for at least two seconds. 
Error message
*1 If not recovered by this action, there may be a possibility of a failure 
or permanent damage. In this case, change the amplifier unit.
*2 Bank switching, reset input, and preset input are available even 
during "com.Loc".
No.
Item Description
Calibration 
function setting
Set the calibration function.
-
1st point 
detection/capture
Set the zero point (1st point).
2nd point target value
Set the target value of the span adjustment (2nd point).
-
2nd point 
detection/capture
Set the detection position for the span 
adjustment.
OFF
 Jam detection function
ON
User
MODE
Not available to set on the main unit that selects "CAL.noH" in [ Calculation mode], and 
 the main unit and expansion unit that selects values other than "t-in" in [ Timing type].
Reference
 position fixed
Jam detection teaching
Only available when "USEr" is selected in [ Jam detection function].
MODE
Setting value 
input screen
Only available when "USEr" is selected in [ Jam detection function].
 Jam detection check point setting
GT2-71
Right Arrow button
[MODE] button
Main screen
Default
Adjustment
 Calibration function setting 
MODE
Detect 1st point
Blink alternately
Capture the 
detection value
 1st point detection/capture
 Only available when "AdJ" is selected in [ Calibration function setting].
*Target value for the first point is the preset value.
Setting value 
input screen
 2nd point target value setting
MODE
Error display Cause Corrective action
The sensor head cable is 
disconnected.
Connect the sensor head to the 
amplifier.
• The sensor head cable is broken.
• The sensor head is damaged.
Change the cable or sensor 
head.
An overcurrent is present 
in the output line.
• Check that the load is within the rating.
• Check that the output line is not 
contacting other lines and frames.
Failed to write/read data.
Recycle power to the equipment 
and perform initialization.
*
1
Spindle movement is not detected
• If something is caught in the spindle, causing the 
spindle not to move, change the sensor head.
• Check the external timing input. (Press the 
SET button to reset.)
The value fell below (rose 
above) the timing level 
during the delay time.
Change the delay timer time 
setting. (Press the SET button 
to reset.)
When setting the internal 
timing, detection was 
completed when the value fell 
below (rose above) the timing 
level before the criterion value 
(P.V. value) is fixed.
The value should not fall below (rise 
above) the timing level before the 
criterion value is fixed. Alternatively, 
lengthen the static hold delay 
stabilizing amplitude so that the 
criterion value can be easily fixed.
Contact between the 
amplifiers is lost.
After turning OFF the power, check the 
connection between the amplifiers.
• In the case of using the 
calculation function, the number 
of the expansion unit when the 
power is turned ON differs from 
the number of the expansion 
unit in the memory of the main 
unit when the calculation is set.
• When using the calculation 
function, a model other than the 
GT2 Series is added.
• Reset the calculation mode or 
perform the initial reset of the 
main unit.
• After turning OFF the power, 
check the connections 
between the amplifiers.
• When using the reference difference 
(rEF) calculation function, an error 
occurred in the main unit.
• When using other than the reference 
difference (rEF) calculation function, an 
error occurred in an expansion unit.
Check each main/expansion 
unit for the cause of the error.
The sensor head is connected 
to the main unit in which the 
calculation only mode is set.
Remove the sensor head from the 
main unit or set the mode other 
than the calculation only mode.
"com.Loc" is displayed 
and cannot change the 
setting.
The read/write setting switch of 
the connected communication 
unit DL-RS1A is set to RW.
*2
 Set 
the read/write setting switch to R.
Refer to "RS-232 Communication 
Unit DL-RS1A User's Manual"
Displayed when this equipment is 
accessed (operation command/
settings and status writing/keylock) via 
<DL-CL1>, <DL-DN1> or <DL-EP1>.
The buttons are locked, but after 
approximately 10 seconds, "com.unLoc" 
is displayed on the amplifier and the 
buttons are unlocked.
*2
The calculation mode is 
used, so the function 
setting mode cannot be 
changed
Check the calculation mode settings 
again.The function setting mode can be 
changed only when the calculation mode of 
the main unit is set to C0. oFF or C5. rEF.
The criterion value (P.V. 
value) becomes "------" 
during the tolerance tuning.
Perform the timing input and fix 
the criterion value, and then 
perform the tolerance tuning.
The hold detection is selected or the 
timing input is not performed, so the 
criterion value (P.V. value) is not fixed.
Perform the timing input.
The operations of the expansion unit 
are locked while the simultaneous 
input is selected and the keylock is 
activated on the main unit.
Deactivate the keylock on the 
main unit.
After ALL GO is selected in 
the special output setting, 
the number of expansion 
units changed.
• If the number of expansion units 
has been changed, set the special 
output setting again.
• If the number of expansion units has 
not been changed, check if each 
expansion unit operates correctly, 
then turn on the power again.
Detect 2nd point
Blink alternately
Capture the
 detection value
 2nd point detection/capture










