Owner's manual
4-6 2-output Settings ( )
4
Settings for Advanced Functions
4-36
- Digital Fiber Sensor FS-N10 Series User's Manual -
Limit setting output mode
Setting output 2 to "LiMt" (limit setting output mode) enables detection of reductions in
received light intensity for output 1. Specifically, if the cumulative minimum of peak
value for output 1 falls below the limit setting value, it is recognized as a reduction in
received light intensity and therefore output 2 is turned on.
"Light intensity hold display" (page 4-25)
Timing chart
For period (1), the peak value 
is not below the limit setting 
value, so output 2 remains 
OFF.
For period (2), the peak value 
is below the limit setting value, 
so output 2 turns ON.
For period (3),
 the peak value 
again is above the limit setting 
value, so output 2 turns OFF if 
Auto (Auto) is selected. If USEr 
(User) is selected, the 
cumulative minimum of peak 
values is the peak value 
during period (2), which is below the limit setting value, so output 2 remains ON.
How to reset after the output is activated
Refer to page 4-3 "2-output Settings ( )" for setting methods.
OFF
ON
Received light intensity
Peak hold value
Limit setting for output 2
Setting value of received
light intensity for output 1
Output2
(When  is selected)
Output2
(When  is selected)
Output1
OFF
ON
OFF
ON
(2)(1) (3)
Display Resetting method
USEr (User)
User reset
 - Press and hold the [MODE] and [SET] buttons simulta-
neously.
 -Execute reset using external input.
 - Cycle the power.
Auto (Auto)
Auto reset
 - Press and hold the [MODE] and [SET] buttons simulta-
neously.
 -Execute reset using external input.
 - Cycle the power.
 - When "peak value > setting value + hysteresis" 