Owner's manual
4-3 Detection Settings (Func)
4
Settings for Advanced Functions
4-11
- Digital Fiber Sensor FS-N10 Series User's Manual -
DATUM2 mode
In DATUM2 mode, the light intensity received 
without a workpiece is always corrected to 
".0". The setting value is also corrected 
according to the correction amount, so that 
the ratio of setting value and received light 
intensity is kept constant, with the result of 
stable detection. The display of the setting 
value does not change.
The DATUM mode is effective in environments where received light intensity varies
gradually, for example where the sensor head is prone to contamination or large
temperature changes.
Sensitivity setting in DATUM2 mode
The sensitivity setting procedure 
below is an example of two-point 
calibration (where the received light 
intensity is ".0" when a workpiece is 
absent and "80.0" when a workpiece 
is present) using the thrubeam/
re
tro-reflective model.
1
Press the [SET] button with no work-
piece present.
2
Press the [SET] button with a work-
piece present.
The light intensity received in the full-light 
receiving state is displayed as ".0".
Refer to page 4-2 "Detection Settings (Func)" for setting methods.
"5.0"
(Initial value)
".0"
Fixed proportion
Received light intensity
Setting
value
.0
100.0
.0
40.0
40.0
80.0
Calibration point (Step 1)
Calibration point (Step 2)
1
2
The DTM indicator
lights up.
Display changes
to "
.0".