Owner's manual
3
Basic Operation
3-5
- Digital Fiber Sensor FS-N10 Series User's Manual -
3-3
Adjusting Sensitivity
This manual refers to the values that select ON/OFF output of the sensor amplifiers as
"Set values." In addition, the manual refers to the adjustment of set values as "Adjusting
Sensitivity." This section describes the sensitivity adjusting method.
Sensitivity adjusting method for the FS-N10 Series is broadly divided into two categories: 
① Preset
Simple operation allows sensitivity adjustment concurrently with correction of the 
received light intensity to "100.0" or "0.0"
This function helps preventive maintenance by eliminating dispersion of the received 
light intensity due to the contents of detection or individual workpieces.
However, this is not suitable for detection of transparent workpiece because there is a 
small difference in the received light intensity between presence and absence of a 
workpiece. 
② Calibration
Sensitivity can be adjusted by a simple operation. This function does not correct the 
received light intensity.
This function is applied for using the received light intensity without correction or for 
high-precision detection.
Calibration is also available in a preset state.
How to select sensitivity adjusting method
List of Sensitivity Adjusting Methods
Sensitivity 
adjusting 
method
Status of use Functions Contents Reference
Preset
Basics
Using thrubeam/retro-reflective 
models
Preset
When there is no workpiece, by sim-
ply pressing the PRESET button, 
sensitivity adjustment is completed.
3-6
Using reflective model
Preset to maxi-
mum sensitivity
When there is no workpiece, by sim-
ply holding the PRESET button, 
sensitivity adjustment is completed.
3-8
At times 
like this
Not successfully displaying the 
intensity level as "100.0" and 
".0" depending on the presence 
of a workpiece.
Work preset
The status in which "100.0" or ".0" is 
displayed can be set at your choice
3-7
Mobile object moves fast
Full automatic 
preset
Preset is enabled by using a fast-
moving wo
rkpiece.
3-9
Calibration
Basic
Us
ing thrubeam/retro-reflective 
models
Two-point 
calibration
The setting can be established just 
by pressing the [SET] button once 
when a workpiece is present and 
absent.
3-11
At times 
like this
Mobile body moves fast
Full automatic 
calibration
Calibration is enabled by using a 
fast-moving workpiece.
3-13
Using the unit in the environ-
ment that tends to get dirty 
easily.
Maximum sensi-
tivity calibration
The setting seldom causes malfunc-
tion even in the environment that 
tends to get dirty easily. 
3-12
Using the unit for positioning
Positioning cali-
bration
The setting suitable f
or positioning is 
available.
3-14
Using the unit for
 high-preci-
sion detection
Percentage cali-
bration
Effective for making correction from 
external devices such as PLC.
3-15