User Manual
5-2 Troubleshooting
5-5
5
Appendix
- DeviceNet Compatible Network Unit DL-DN1 Userโs Manual (GT-70A) -
๎ Sensor communication indicator
This lamp indicates whether the DL-DN1 is communicating properly with sensor
amplifiers.
The cause of the error can  be identified by reading the error code through I/O
communication or explicit messaging.
"Error information list" (page 3-8)
LED status Condition Corrective action
Not lit Power is not supplied to the 
DL-DN1.
Check that the DL-DN1 is cor-
rectly connected with the sensor
amplifiers.
Green Solid Communicating correctly. -
Flashing In process of power-on 
reset.
After the power-on reset time 
has elapsed, the DL-DN1 auto-
matically switches to the norma l 
state.
Red Flashing at 
fixed inter-
vals
Temporarily unable to com-
municate with sensor ampli-
fiers.
Check for any noise sourc
e 
around the DL-DN1. (The error 
is au tomatically corrected after 
the cause is removed.)
Repeating 
of 4 con-
secutive 
flashes
Model error (0003h) Connect a sensor amplifier of a 
compatible model.
Mixed connection error 
(0004h)
Remove the incompatible sen-
sor amplifier.
Number-of-units error 
(0006h)
Observe the number of connect-
able sensor amplifiers.
Solid Initialization error
(0001h/0002h/0005h)
Check the nu mber of connected 
sensor
 amplifie
rs and the con-
nection to the sensor amplifiers, 
and then cycle power. If the 
error can not be restored, con-
tact your nearest sales office.
Sensor-to-sensor communi-
cation error
(0007h)
Check the connections of the 
sensor amplifiers, and then 
cycle power.