User guide

3-3 Explicit Messaging
3-33
3
Communicating with the IL Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (IL) -
Nx10+4
69
Averaging/Diff. count filter/High-pass
filter
R/W 4
0: 1 time
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
6: 64 times
7: 128 times
8: 256 times
9: 512 times
10: 1024 times
11: 2048 times
12: 4098 times
13: Diff. count filter
14: High-pass filter
6A
Output mode
R/W 0
0: N.O.
1: N.C.
6B
Reserved
6C
Hold function setting
R/W 0
0: Sample hold
1: Peak hold
2: Bottom hold
3: Peak-to-Peak hold
4: Auto peak hold
5: Auto bottom hold
6D
Auto peak hold or auto bottom hold
trigger level
*4 R/W 1.000
-99.999 to +99.999
6E
Timing input setting
R/W 0
0: Level
1: Edge
6F
Delay timer
R/W 0
0: OFF
1: On delay
2: Off delay
3: One shot
70
Timer duration
R/W 60
5 to 9999
71
Hysteresis
R/W 0
0 to 99.999
72
Analog output scaling
*16 R/W 0
0:Initial state
1: Free range
2: Bank
73
Analog output upper limit
*4
*16
R/W 10.000
-99.999 to +99.999
74
Analog output lower limit
*4
*16
R/W
-10.000
-99.999 to +99.999
75
External input setting
*17 R/W 0
0: Initial state
1: User setting
76
External input 1
*17 R/W 0
0: Zero shift input
1: Bank A input
2: Bank B input
3: Laser emission stop input
4: Not use
77
External input 2
*17 R/W 0
0: Reset input
1: Bank A input
2: Bank B input
3: Laser emission stop input
4: Not use
78
External input 3
*17 R/W 0
0: Timing input
1: Bank A input
2: Bank B input
3: Laser emission stop input
4: Not use
79
External input 4
*17 R/W 4
0: Not used
1: Bank A input
2: Bank B input
3: Laser emission stop input
InstID
(DEC)
AttrID
(HEX)
Name
Description
Attribute
Default
value
Parameter range