User guide
3-3 Explicit Messaging
3-31
3
Communicating with the IL Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (IL) -
Nx10+1
70
Timing status
R
0: During sampling
1: Not during sampling
71 to
75
Reserved
76
Laser emission stop status
R
0: Laser emitting
1: Laser stopped
77
Abnormal setting
*8 R
0:
Normal setting
1: Abnormal setting
78
External input status
*20 R
0 to 15
79
EEPROM writing result
*9 R 1
0: Writing
1: Normal termination
2: Abnormal termination
7A
Zero shift/Zero shift reset result
*10 R 1
0: Executing
1: Normal termination
2: Abnormal termination
7B
Reset execution result
*10 R 1
0: Executing
1: Normal termination
2: Abnormal termination
7C
System parameter current state
*11 R 0
Main unit: 0 - 9
Expansion unit: 0 - 1
7D to
7F
Reserved
80
Tuning result
*12 R 1
0: Executing
1: Normal termination
2: Abnormal termination
81
Calibration result
R1
0: Executing
1: Normal termination
2: Abnormal termination
82 to
83
Reserved
Nx10+2
64
Group-2 entry count
R20
65
HIGH setting value (BANK 0)
*4 R/W 5.000
-99.999 to +99.999
66
LOW setting value (BANK 0)
*4 R/W -5.000
-99.999 to +99.999
67
Shift target value (BANK 0)
*4 R/W 0.000
-99.999 to +99.999
68
Analog output - upper limit value
(BANK 0)
*4
*16
R/W 10.000
-99.999 to +99.999
69
Analog output - lower limit value
(BANK 0)
*4
*16
R/W
-10.000 -99.999 to +99.999
6A
HIGH setting value (BANK 1)
*4 R/W 5.000
-99.999 to +99.999
6B
LOW setting value (BANK 1)
*4 R/W -5.000
-99.999 to +99.999
6C
Shift target value (BANK 1)
*4 R/W 0.000
-99.999 to +99.999
6D
Analog output - upper limit value
(BANK 1)
*4
*16
R/W 10.000
-99.999 to +99.999
6E
Analog output - lower limit value
(BANK 1)
*4
*16
R/W
-10.000 -99.999 to +99.999
6F
HIGH setting value (BANK 2)
*4 R/W 5.000
-99.999 to +99.999
70
LOW setting value (BANK 2)
*4 R/W -5.000
--99.999 to +99.999
71
Shift target value (BANK 2)
*4 R/W 0.000
-99.999 to +99.999
72
Analog output - upper limit value
(BANK 2)
*4
*16
R/W 10.000
-99.999 to +99.999
73
Analog output - lower limit value
(BANK 2)
*4
*16
R/W
-10.000 -99.999 to +99.999
74
HIGH setting value (BANK 3)
*4 R/W 5.000
-99.999 to +99.999
75
LOW setting value (BANK 3)
*4 R/W -5.000
-99.999 to +99.999
76
Shift target value (BANK 3)
*4 R/W 0.000
-99.999 to +99.999
77
Analog output - upper limit value
(BANK 3)
*4
*16
R/W 10.000
-99.999 to +99.999
InstID
(DEC)
AttrID
(HEX)
Name
Description
Attribute
Default
value
Parameter range