User guide
3-3 Explicit Messaging
3-27
3
Communicating with the IL Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (IL) -
*1 The function of DL-DN1 only, which responds to explicit messaging synchro-
nously with I/O communication. This function does not guarantee synchronism 
of the whole system, including PLC or master equipment.
0
69 to 6B System reserved
6C Error ID number
Error details.
If there are errors with multiple ID 
numbers, the error information for the 
smallest ID number is output.
RUINT0
Error information list
(page 3-8)
6D Error code R UINT0
6E
Warning ID 
number
Not used with the IL Series.
RUINT0
−
6F Warning code R UINT0
70 to 73 System reserved
74 HIGH
The HIGH state is output by assigning 
sensor amplifiers (ID 01 to ID 15) bits 
0 - 14.
RWORD0
0: OFF
1: ON
75 LOW
The LOW state is output by assigning 
sensor amplifiers (ID 01 to ID 15) bits 
0 - 14.
RWORD0
0: OFF
1: ON
76 GO
The GO state is output by assigning 
sensor amplifiers (ID 01 to ID 15) bits 
0 - 14.
RWORD0
0: OFF
1: ON
77 Alarm output
The alarm output is output by assign-
ing sensor amplifiers (ID 01 to ID 15) 
bits 0 - 14.
RWORD0
0: OFF
1: ON
78 (Not used)
79 to 8C System reserved
8D
Judgment value 
"invalid"
If the judgmentd values for sensor 
amplifiers (ID 01 to ID 15) are "invalid" 
(-----), they are output by assigning 
them to bits 0 - 14.
RWORD0
0: Normal value
1: Invalid
8E
Judgment value 
"under"
If the judgmentd values for sensor 
amplifiers (ID 01 to ID 15) are "under," 
they are output by assigning them to 
bits 0 - 14.
RWORD0
0: Normal value
1: Under
8F
Judgment value 
"over"
If the judgmentd values for sensor 
amplifiers (ID 01 to ID 15) are "over," 
they are output by assigning them to 
bits 0 - 14.
RWORD0
0: Normal value
1: Over
90
Current value ID 
01
Reads the current value of ID 01.
Same as the current value used in I/O 
communication.
R
DINT
0
-2147483648 to 
2147483647
~
9E
Current value ID 
15
Reads the current value of ID 15.
Same as the current value used in I/O 
communication.
9F to B0 System reserved
B1
Number of 
sensor amplifier 
units connected
Reads the number of connected sen-
sor amplifiers.
RUINT 0 1 to 15
B2 to B3 System reserved
B4
Explicit message 
response method
If synchronous response is used, 
response occurs synchronously with I/
O communication.*1
R/W UINT0
0: Immediate 
response
1: Synchronous 
response
B5 to B9 System reserved
BA
Operating mode 
switch status
Set status of operating mode setting 
switch: switch 1 (LSB) to switch 4 
(MSB)
RUINT0
0 to 15
0: OFF, 1: ON
InstID 
(DEC)
AttrID
 (HEX)
Name Description
Attribute
Data 
type
Default 
value
Parameter range