User guide
3-2 I/O Communication
3-5
3
Communicating with the IL Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (IL) -
Configure the operating mode setting switch to suit the operating mode to be used.
"Configuring the Operating Mode Setting Switch" (page 3-5)
The memory size occupied by the DL-DN1 varies with the selected operating mode
and the number of connected sensor amplifiers.
3-output mode
Configuring the Operating Mode Setting Switch
DIP switch Operating mode
1 2 3 4 Output
Current
value
External
input
BANK
change
Setting value
rewrite
OFF OFF OFF OFF
3-output
No
No
No
No
OFF ON OFF OFF Yes
OFF OFF OFF ONNo
3-input
OFF ON OFF ON Ye s
OFF OFF ON OFF No
Ye s
OFF ON ON OFF Yes
OFF OFF ON ONNo
NoYes
OFF ON ON ON Ye s
ON OFF OFF OFF
5-output
No
No
No
No
ON ON OFF OFF Yes
ON OFF OFF ONNo
5-input
ON ON OFF ON Ye s
ON OFF ON OFF No
Ye s
ON ON ON OFF Yes
ON OFF ON ONNo
NoYes
ON ON ON ON Ye s
Occupied Memory
3-output
No extended mode Ye s - - -
3-input - Ye s Ye s Ye s
BANK change - - Ye s -
Setting value rewrite - - - Ye s
Area IN OUT IN OUT IN OUT IN OUT
Number of sensor amplifiers 1-8 8 0 14 6 18 10 22 24
(bytes)