Manual
5-2 Troubleshooting
5-4
- DeviceNet Compatible Network Unit DL-DN1 Userโs Manual (FD-MH) -
5
Appendix
๎ Network status indicator (NS)
This lamp indicates whether the DL-DN1 is properly communicating with the
DeviceNet.
LED status Condition Corrective action
Green Solid Communicating properly. -
Flashing The DL-DN1 is connected 
to the network, but the com-
munication with the master 
unit is not established.
Check that the DL-DN1 is regis-
tered in the master unit.
The DeviceNet cable was 
disconnected while in oper-
ation.
Check that the DeviceNet cable 
is connected correctly.
Red Solid Network error. Check that the node address of 
the DL-DN1 is not duplicated 
with that of another slave unit.
Flashing Minor network error. Check that the data link is prop-
erly configured, and then cycle 
power.
G
reen/
red
Flashing The DL-DN1 is checking its 
operation in the power-on 
process.
After completing the check, the 
DL-DN1 automatically switches 
to the normal state.
Not lit Not connected to the net-
work.
Check that the DL-DN1 is cor-
rectly connected with the sensor 
amplifiers.