User Manual
3-2 Device Maps
3-6
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
Communicating with the FD-MH series
3
Number [n] denotes the first relay number assigned to the DL-CL1.
*1 See  "Entering an External Input into a Sensor Amplifier" (page 3-17).
*2 See  "Reading Cu rrent Values (Instantaneous Flow Rate) from Sensor Amplifiers" (page 3-18).
*3 See  "Reading/Writing Settings or Status of a Sensor Amplifier" (page 3-21).
See  "Issuing a Motion Command to a Sensor Amplifier" (page 3-20).
 Remote Register RWr (DL-CL1 -> Master Station)
 Operating 
mode 
 Device 
no. (HEX) 
 Name 
 Communication 
method 
 Description Writing range 
 Monitor mode  1 
 RY[n] + 40 
to 49 
 (Not used)   - - 
 RY[n] + 4F 
to 50 
 System reserved - Unusable 
 RY[n] + 51 
 Request for 
command 
 *3 
 Used when communicating under handshake 
control program.
  This is input when requesting command 
execution. 
 0->1: Request 
execution 
 RY[n] + 52 System reserved - Unusable 
 RY[n] + 53 
 Current Value 
Update Request 
 - 
 Used to lock data update in current value 
boxes (RWr[n] + 08 to 0D).
This may be used to obtain the current values 
of multiple sensor amplifi ers at the same 
timing.
The current value is locked while the update 
request is held.
The update lock state can be checked by the 
current value update lock state (RX[n] + 53). 
 0: Do not lock 
update
1: Request 
update lock 
 RY[n] + 54 
to 5D 
 System reserved - Unusable 
 RY[n] + 5E 
 Request to 
change current 
value page 
 *2 
 Used for reading the current value. 
 This is input when requesting to change the 
current value page (the ID number of the 
sensor amplifi er to read from). 
 0->1: Request 
change 
 RY[n] + 5F S
ystem reserved - Unusable 
 RY[n] + 60 
to 69 
 (Not used)   - - 
 RY[n] + 6F (Not used)   - - 
 Operating 
mode 
 Device no. 
(HEX) 
 Name 
Communication 
method 
 Description 
 Reading 
range 
 Small-memory mode  1 
 Small-memory mode  2 
 Monitor mode  1 
 RWr[n] + 00   Error code   - 
 Stores an error code when error state (RX[n] + 0F) 
turns ON. 
 *4 
 RWr[n] + 01 
 Command 
response 
 *3 
 Used for communicating under handshake control 
program. Stores details of command execution result. 
 *5 
 RWr[n] + 02 to 
03
(2 words) 
 Read data   *3 
 Used when communicating under handshake control 
program.
Stores the parameter data read from the sensor amplifi er. 
 *6 