User Manual
3-1 CC-Link Communication and Operating Modes
3-3
3
Communicating with the FD-MH series
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
Select an operating mode of the DL-CL1 to suit the functions of the sensor amplifiers
to be used.
The  specific CC-Link device configu ration  and the data that can  be communicated
using cyclic transfer vary with each operating mode of the DL-CL1. An appropriate
operating mode should  be determined by considering the number of link points the
data that can be communicated.
 "Configuring the Data Link" (page 2-
10)
Ye s: Available with sensor amplifiers of ID 01 to 10. No: Not available.
*1 For details of the functions assigned for motions commands and setting/status read/write, see  
"Device Maps" (page 3-4) and  "Command Parameter List" (page 3-24).
*2 In remote register RWw, specify the ID number of the sensor amplifier from which to read.
*3 To use this communication method, crea te a program that controls commands by handshaking 
between a remote input/output and
 remote register.
*4 It is possible to read instantaneous flow rate or rewrite setting value regardless of the detection 
mode setting.
Selecting an Operating Mode of the DL-CL1
Method of 
communication 
with the master 
station
Available function 
of sensor 
amplifier
*1
Operating mode of DL-CL1
Reference 
page for
communication 
method
Small-
memory 
mode 1
Small-
memory 
mode 2
Monitor 
mode 1
Monitor 
mode 2
Full
mode 1
Full
mode 2
1-station, 
1x
2-station, 
1x
4-station, 
1x
1-station, 
8x
4-station, 
2x
2-station, 
8x
p. 3-4 p. 3-10
Remote input RX Read out-
puts 1 - 5
Output 1
Ye s Ye s Ye s Ye s Ye s Ye s 3-4
Output 2
No Yes Ye s Ye s Ye s Ye s
Output 3
No Yes Ye s Ye s Ye s Ye s
Unused
------
Unused
------
Remote register RWr Read current value 
(instantaneous flow 
rate)
*4
No No
Ye s
*2
Ye s Ye s Ye s
3-6
Remote output RY External 
inputs 1-5
Integration 
reset
Ye s Ye s Ye s Ye s Ye s Ye s
3-12
Flow rate 
hold reset
No Yes Ye s Ye s Ye s Ye s
Unused
------
Te m p e r a-
ture hold 
reset
No No Yes Ye s Ye s Ye s
Unused
------
Remote register 
RWw
Rewrite setting 
value
*4
No No No No Yes Ye s
3-16
Handshake control 
program
*3
(Command commu-
nication)
Motion command No No Yes Ye s Ye s Ye s 3-20
Read output
No No Yes Ye s Ye s Ye s
3-17
Read current value
Read setting/status
Write setting/status