User Manual
2-10
2
Connection and Configuration
- CC-Link Compatible Network Unit DL-CL1 Userβs Manual (FD-MH) -
2-3
Configuring the Data Link
Use the following configuration procedures for connecting the DL-CL1 to the CC-Link
system.
This manual covers only the functions and settings of a CC-Link mas-
ter station which are required for communication with the DL-CL1. For 
the functions and settings related to the communication between the 
CC-Link master unit and CPU unit, refer to the manuals shipped with 
your master unit or CPU unit.
To connect the DL-CL1 to the CC-Link master  unit, it is necessary to configure the
slave attribute and memory allocation settings.
ξ Slave attribute settings
Register the DL-CL1 to the CC-Link master unit as a remote device station.
Yo u ca n also configure the settings by importing a CSP file into the software for the
master unit (ladder programming software or CC-Link configuration software).
The CSP file can be downloaded from the KEYENCE web site
:
http
://www.keyence.com
ξ Memory allocation settings
In order to exchange data  between the DL-CL1 and CC-Link master station, configure
the memory allocation  settings  using the software for the master  station (ladder
programming software or CC-Link configuration software).
Where multiple slave units are connected, the memory allocation for each
slave  unit is  done automatically  based on the spe
cified  start
ing address.
The  allocation information for each  slave  unit can  be checked using the
CC-Link configuration software.
Use the following procedures to configure the data link of the DL-CL1.
Point
Configuring the Master Station
Reference
Reference
Configuring the DL-CL1
Operating mode setting switch
Transmission rate 
 setting switch
Station number 
setting switch