User guide
5
13
. Ambient Pressure Compensation
Open the applied pressure to the surrounding air so that it equals the 
ambient pressure and press the   button for 3 seconds or more 
while the current value or reference value is being displayed.
The ambient pressure point will be corrected.
*1  Ambient pressure can be corrected within a range of ±5 % of F.S. 
  When atmospheric pressure compensation has been performed, the 
settings will be saved even when power to the sensor is turned off.
*2  AP-C31/C31P/C33/C33P: Can be used during focus mode operation 
as well. Values will be compensated based on the center pressure.
14
. Key Lock
Disables operations that would modify the sensor’s configuration. Display 
content can be toggled. 
Pressing and holding either   or   for at least 3 seconds while pressing 
 button will lock the keypad and cause the   display to flash.
 * The same key combination will deactivate the key lock feature.
11
. Default Mode Settings (Initialization)
The sensor ships with the following configuration.
Detection range
Detection mode
Operating mode
N.O./N.C. switching
Analog/zero shift
*
Chatter prevention
Display color
Power-save
AP-C30/C35
AP-C31/C31P/C33/C33P
 * Press   button 5 times while holding down the   button to return the 
sensor to its default configuration.
12
. Specifications
101.3 to -101.3 kPa
    (-10 to 10.00 kPa) 
     0 to -101.3 kPa
    (0 to -10.00 kPa) 
    0 to +101.3 kPa
(0 to +10.00 kPa)
Environmental 
resistance
Multi-range    Negative pressure Positive pressure
AP-C30/C35 AP-C31/C31P AP-C33/C33P
500 kPa
(25 kPa)
500 kPa  1.5 MPa 
Air, non-corrosive gasses
Gauge pressure
12 to 24 VDC10% Ripple (P-P) 10% max.
3.5 digit two-color 7 segment LED (11 mm character height) 
Display cycle: 10 times/second
-10 to +110% of F.S.  -15 to +110% of F.S.
  Red LED x 2 (supports control output 1 / control output 2)
0.2 kPa
(0.02 kPa)
0.1 kPa
(0.01 kPa)
0.1 kPa
(0.01 kPa)
0.1 kPa 0.001 MPa 
0.01 kPa 0.1 kPa
   Variable (standard 0.5% of F.S.)
1% of F.S. max.
Selectable from 2.5, 5, 100, 500 ms 
No-voltage input (without contacts) 
Input time 2 ms or greater (Switchable with analog output.)
NPN open collector max. 100 mA (40 V max.)
 residual voltage 1 V max., 2 outputs (NO/NC switchable)
*3 PNP open collector Max. 100 mA (30 V max.)
 residual voltage 1 V max., 2 outputs (NO/NC switchable)
1 to 5 V Output impedance 1 kΩ max. (Switchable with zero shift input.)
0 to +50 C (No freezing)
35 to 85 % RH (No condensation)
10 to 55 Hz, compound amplitude 1.5 mm, 2 hours for each of XYZ axes
Rc(PT)1/8 Bidirectional rotating type
Front case: polysarfun; Rear case: PBT; 
Front sheet: polycarbonate; Pressure port: die-cast zinc
Approx. 30 g (not including cables) / Approx. 85 g (including 2-m cable) 
Power cord (2-m, connector type), Units sticker *4
0 to -101.3 kPa  0 to 1.000 MPa
Type
Model
Rated pressure
range
( ) : AP-C35
Pressure resistance
( ) : AP-C35
Adaptive uids
Pressure type
Power supply voltage
Current 
consumption
Display method
Conguration/
display range *1
Operating status indicators
Multi-range
( ) : AP-C35
Standard mode
Focus mode
Hysteresis *2
Display temperature 
characteristics
Response (chatter
prevention feature)
Zero shift input
Control output
Analog output
Ambient temperature
Relative humidity
Vibration
Pressure port
Housing material
Weight
Accessories
ResolutionRating
  Negative 
pressure 
  Positive 
pressure
Compound 
pressure
Compound 
pressure
  Negative 
pressure 
  Positive 
pressure
Eco mode
480 mW(40 mA)/600 mW(50 mA) max. 720 mW(30 mA)/960 mW(40 mA) max.
Normal
720 mW(60 mA)/900 mW(75 mA) max.
960 mW(40 mA)/1320 mW(55 mA) max.
12 V operation(NPN/PNP) 24 V operation(NPN/PNP)
*1 During focus mode operation, restricted to focus range.
*2 During focus mode operation, standard 0.2% of F.S.
*3 AP-C31/C31P are PNP output types.
*4 AP-C33/C33P only.
15
. Error Displays and Corrective Actions
■
 Error displays during normal operation
•  No difference in sensitivity 
(during 2 point tuning/active 
tuning).
•  There is an applied pressure 
of 5 % of F.S. during ambient 
pressure compensation.
•  An excess current is flowing to the 
control output.
•  Reading is falling below 
(exceeding) configuration/display 
pressure range.
•  Reading is exceeding (falling 
below) configuration/display 
pressure range.
•  When there were not at least 2 
shift inputs during active 2 point 
tuning.
Adjust the air pressure device so that 
there will be a difference in sensitivity.
(Return to  atmospheric pressure.) 
Repeat atmospheric compensation.
Check  the  load  and  return  it  to  the 
rated range.
Return  the  pressure  to  the  rated 
pressure range.
Return  the  pressure  to  the  rated 
pressure range.
Repeat the active tuning procedure so 
that there are at least 2 shift inputs.
  Display  Cause  Solution
*  Contact KEYENCE for information about error displays other than those 
described above.