Tus neeg siv phau ntawv
Clima Flex Wall Mounted FCU (S type panel) CLIFC-W 2015-05
20
False installation
Drilling a hole
Determine the pipe hole position using the installation board, and drill the pipe hole (N95mm) so it slants
slightly downward.
Always use a wall hole conduit when piercing metal lath, ply wood or metal plate.
12.4.3 Connective and drain pipe installation
Drain pipe installation
Run the drain hose sloping downward. Do not install the drain hose as illustrated below.
When connection extended drain hose, insulate the connecting part of extended drain hose with a
shield pipe.
Connection pipe installation
For the left-hand and rear-left-hand piping, install the piping as shown. Bend the connective pipe to be
laid at 43mm height or less from the wall.
mounting
board
of ind
oor unit
horizontal line
mounting
board
of indoor unit
horizontal line
Do not form a rise
Do not put the hose
end into water
Shield pipe
Wall
Drain hose
Extended drain hose
Right piping
Left piping
Right back piping
Left back piping