User manual
75        PBS/PBJ-BA-e-1314 
17.4  User Settings 
17.4.1  Overview 
This menu is used to determine technical data of communication between the 
balance and a computer or electronic printer. 
Note: 
This menu applies both to the RS-232C interface and DATA I/O interface. 
For the device to which the DATA I/O interface is connected e.g. electronic printer, 
the balance communication parameters should be set to the standard settings i.e. 
select the following menu elements:  76, 77, 83, 89, 92, 94. 
17.4.2  Handshaking 
The handshake function determines whether or not peripheral devices can receive 
communication data from the balance. It does not transfer the balance status to the 
peripheral devices. The balance can receive data as long as there is a free space in 
its receive buffer memory. This function is ready for operation when the „oFF” symbol 
is displayed. Its reliable operation in other states cannot be guaranteed. 
If the balance data output is interrupted by the handshake function, the balance 
display is locked. 
Enter the suitable settings for the handshake function.  
If the software handshake function is not to be performed, select the menu 
element 
73 
If the software handshake function is to be performed in the way described 
below, select the menu element  
•  When the X-OFF (13H) command is received by the balance, the 
balance data output is stopped. 
•  When the X-ON (11H) command is received by the balance, the 
balance data output is started.  
74 
If the hardware handshake function is to be performed in the way described 
below, select the menu element  
•  If the DTR parameter is set to OFF, the balance data output is 
stopped. 
•  If the DTR parameter is set to ON, the balance data output is 
started. 
75 
To call up the time controlled hardware handshake function, select the 
menu element  
76 