Figure 6: Floor Control Relay Connection
5.2.2 RS-485 Controller Network
All of the controllers in the elevator network communicate through an RS-485 serial
communication network. Per the RS-485 industry specification, this network must be daisy-
chained, with a total network cable length of no more than 16,000 feet. Make the RS-485 network
connections per the information in Table 2 and Figure 7 on page 12.
NOTE: Do NOT connect earth ground to the RS-485 network cable shield.
Table 2: RS-485 Controller
Network
TB-1 Pin Description
1 Tx/Rx Negative
2 Tx/Rx Positive
3 Network Cable Shield