Quick Start GuideLC-502P/LC-508P
4.2 Do Not
Make modem phone line connections through PBX telephone switching systems - most
modems are not compatible with PBX systems leading to disconnection problems with the
modem.
Locate a LC-500P controller near EMI sources - EMI sources can affect the performance of the
controller.
Locate a reader near EMI sources - EMI sources can affect the performance of the reader.
Use non-approved switching power supplies, or high noise/high ripple current - they are EMI
sources.
Route network and reader cables beside power cables - transients on the power cables may be
picked-up by network and reader cables.
Stretch or over-tension cables.
Route cables over sharp objects.
Let the cables get tangled.
Mix LC-500Ps with PXL-100s in the same network.
Connect earth ground to the network cable shield - the LC-500P automatically connects earth
ground to the shield at one point on the network to prevent ground loops.
Use gender changer plugs when making RS-232 serial communication connections (unless you
know it is a "straight-through" plug) - gender changers may have internal wiring changes that
can disrupt communications.