LC-202W/LC-208WQuick Start Guide
5.4.2 LC-208W/LC-208W Combination
Perform the following wiring instructions to accommodate an elevator application using two LC-
208W panels (up to 16 floors).
1. Make a complete set of connections to the first LC-208W panel. Refer to Section 5.3 on page 16
for all connections to the LC-208W.
2. Daisy-chain the Data0, Ground, and Data1 reader connections from W-TB-B of the second LC-
208W panel to W-TB-C of the first LC-208W panel. Make the connections per the information
in Table 9 and Figure 13 on page 22.
3. Daisy-chain the TxRx+, TxRx-, and Shield Network Communication connections from W-TB-
B of the second LC-208W panel to W-TB-C of the first LC-208W panel. Make the connections
per the information in Table 10 and Figure 14 on page 23.
4. The floor/relay connections for the second LC-208W are made according to the floor/panel
association. Refer to Section 5.3 on page 16 for all floor/relay connections to the LC-208W.
Power connections are made per the instructions in Section 5.2.4 on page 16.
Table 9: LC-208W to LC-208W Panel Wiring Connections
W-TB-B of Second Panel W-TB-C of First Panel
Reader Ground (OUT) Reader Ground (IN)
Data0 (OUT) Data0 (IN)
Data1 (OUT) Data1 (IN)
Table 10: LC-208W to LC-208W Panel Network
Communication Wiring
W-TB-B of Second Panel W-TB-C of First Panel
TxRx - (OUT) TxRx - (IN)
TxRx + (OUT) TxRx + (IN)
Shield (OUT) Shield (IN)