9.1.1 Standard Doors/Gates Properties
Click on Setup > System > Properties (tab) > Doors/Gates.
Each door must be assigned a property set. There are 4 standard property sets that cannot be modified.
However, if these do not fit the necessary requirements, new property sets may be created.
Use the following table to determine whether one of the standard property sets may be used.
Standard 4
Door
Standard 2
Door
Extended 4
Door
Extended 2
Door
Door Type Standard Standard Standard Standard
Auto Unlock/Lock Timezone Never Never Never Never
Unlock Time 10 10 10 10
Extended Unlock Time 20 20 20 20
Open Time 10 10 10 10
Extended Open Time 20 20 20 20
First Person In Not Used Not Used Not Used Not Used
Request To Exit (RTE) 1 Momentary
Unlock
Momentary
Unlock
Momentary
Unlock
Momentary
Unlock
Request To Exit (RTE) 2 Not Used Not Used Not Used Not Used
Door Lock Relay Active Energized Energized Energized Energized
Door Forced Relay Active Not Used Not Used Energized Energized
Door Held Relay Active Not Used Not Used Energized Energized
Alarm Shunt Relay Active Not Used Not Used Energized Energized
Door Switch Contact Type Normally
Closed
Normally
Closed
Normally
Open
Normally
Open
Door Switch Circuit Type None (2 State) None (2 State) None (2 State) None (2 State)
Request To Exit 1 Contact
Type
Normally
Open
Normally
Open
Normally
Open
Normally
Open
Request To Exit 1 Input
Circuit Type
None (2 State) None (2 State) None (2 State) None (2 State)
Request To Exit 2 Contact
Type
Not Used Not Used Normally
Open
Normally
Open
Request To Exit 2 Circuit Type None (2 State) None (2 State) None (2 State) None (2 State)
Latch Integrity Contact Type Not Used Not Used Normally
Closed
Normally
Closed
Latch Integrity Circuit Type None (2 State) None (2 State) None (2 State) None (2 State)