Instruction Manual

2-12 BHK-MG (OPR) 022014
FIGURE 2-4. LOCAL SENSING, SLOW MODE SELECTED, GROUNDING NETWORK CONNECTED,
FLOATING OUTPUT (FACTORY DEFAULT CONFIGURATION)
2.7.5.5 NEGATIVE OUTPUT, POSITIVE TERMINAL GROUNDED
To configure the BHK-MG as a negative output power supply (referenced to ground), connect
the positive output terminal to ground: use a 5-terminal link to connect TB1-4 (GND - CHASSIS)
to TB1-2 (+OUT). Note that when the positive output is grounded, the ground network (TB1-3) is
inoperative (see Figure 2-5).
FIGURE 2-5. REMOTE SENSING, FAST MODE SELECTED, POSITIVE OUTPUT GROUNDED