Owner manual

1-2
ABCOPR040104
TABLE 1-3. ABC SPECIFICATIONS
SPECIFICATION RATING/DESCRIPTION
CONDITION
INPUT CHARACTERISTICS
a-c Voltage nominal 100/120/220/240V a-c Single phase
range 85-264V a-c Wide range
Frequency nominal 50-60Hz
>63Hz Input leakage current
exceeds specifications
range 47-63Hz (400Hz)
Current 85V a-c 1.8A
Maximum at
100W output
120V a-c 1.3A
240V a-c 0.65A
264V a-c 0.60A
Initial turn-on surge 5A peak for <150 usec 85-264V a-c, 0-100% load
Power Factor (min) 120V 0.99
100% load
240V 0.97
EMC immunity to: Radiated RF EN 61000-4-3 level 3
Magnetic Field EN 61000-4-8 level 4
Electrostatic discharge EN 61000-4-2 level 2: contact,
level 3: 8KV air discharge
Conducted RF EN 61000-4-6 level 3
Electrical fast transient EN 61000-4-4 level 3
Surges EN 61000-4-5 level 4
EMC Emissions Conducted EN 55022 Class B 0.15-30 MHz
Radiated EN 55022 Class B 30-1000 MHz
Harmonics Conducted EN 61000-3-2 0-2 KHz
Leakage current 120V a-c <0.25mA
Source frequency in
47-63Hz range
240V a-c <0.5mA
Circuit type PFC Flyback converter
Output Forward converter
Switching Frequency 100KHz
OUTPUT CHARACTERISTICS
Type of Stabilizer Automatic crossover Voltage/Current
Adjustment range 0 to 100% of rating Voltage/Current
Source effect Voltage <0.01% E
O
max
Nominal ±15%
of input voltage
Current <0.01% I
O
max
Load effect Voltage <0.01% E
O
max
0 to 100% load change
Current <0.02% I
O
max
Temperature effect Voltage <0.01% E
O
max
Per degree C
(0 to 50° C)
Current <0.01% I
O
max
Time effect Voltage <0.01% E
O
max
0.5-8.5 hours
Current <0.01% I
O
max
Error sense 0.5V per wire Voltage allowance
Isolation voltage 500V d-c or peak Output to ground