Installation guide

Installation Instructions
HOOD EXHAUST
NOT_ Read these next two pages only if you plan to vent your exhaust to the outside.
If you plan to reclrculate the air back into the room, proceed to page 6.
OUTSIDE TOP EXHAUST (EXAMPLE ONLY)
The following chart desclibes an example of one possible ductwork installation.
EQUIVALENT NUMBER EQUIVALENT
DUCT PIECES LENGTH x USED = LENGTH
RoofCap 24 Ft. x (1) 24 Ft.
12Ft.StraightDuct 12 Ft. x (1) 12Ft.
(6" Round)
Rectangular-to-Round 5 Ft. x (1) 5 Ft.
TransitionAdapter*
Equivalentlengthsof ductpiecesarebasedon actualtests and
reflectrequirementsfor goodventingperformancewith anyventhood.
Total Length = 41 Ft.
*IMPORTANT: ff a rectangular-to-round transition adapter is used, the bottom comers of the damper will have
to be cut to fit, using the fin snips, in order to allow free movement of the damper.
OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
The following chart describes an exmnple of one possible duc ,twork instanadon.
DUCT PIECES
EQUIVALENT NUMBER EQUIVALENT
LENGTH* x USED -- LENGTH
40 Ft. x (1) 40 Ft.
Wall Cap
3Ft. StraightDuct 3 Ft. x (1) = 3 Ft.
(3¼"x 10" Rectangular)
(_ 30° Elbow 10Ft. x (2} 20 Ft.
Equivalentlengthsof ductpiecesare basedon actualteats and
reflect requirementsfor goodventingperformancewith any venthood.
Total Length = 63 Ft.
NOTE: For back exhaust, care should be taken to align exhaust with space between studs, or wall should be
prepared at the time it is constructed by leaving enough space between the wall studs to accommodate exhausL
4