Installation Guide
GAS COOKTOP INSTALLATION INSTRUCTIONS
6
9
Preparing for Ductwork
Cut hole in cabinet wall or oor as appropriate for your
installation. Make sure exhaust duct is located between
wall studs or oor joists. (Figure 9, 10, 11, 12, 13A & 13B)
NOTE: Ductwork MUST be vented to outside.
DO NOT vent into a wall, ceiling, crawlspace, attic or
any concealed space.
When cutting or drilling into wall or
ceiling, DO NOT damage electrical wiring and other
hidden utilities.
Figure 9 – 30" MODEL
BOTTOM DUCTWORK HOLE
Figure 7 –
DUCT THROUGH-THE-FLOOR
Figure 8 –
DUCT THROUGH-THE-WALL
Figure 6 –
DUCT ON-THE-FLOOR
Figure 5 – DUCT TAPE OVER SEAM AND SCREW
8
Installing the Ductwork
Use galvanized or aluminum duct in 6” round or 3¼”
x 10" size, or a combination of both. PVC duct should
be used if installing under a poured concrete slab.
Use the shortest and straightest duct run possible.
For satisfactory performance, the duct run should
not exceed 100 feet equivalent length. Refer to the
“Calculating Duct Length” chart for equivalent lengths.
(see page 14). All duct joints should be fastened with a
screw and sealed with tape as shown in Figure 5.
NOTE: Local building code must be followed in
specifying approved type and schedule of ALL duct
used. Always use an appropriate roof or wall cap with
damper.
Screw
Air Flow
Duct Tape
Over Seam
and Screw
CUTOUT
CENTER
CUTOUT
CENTER
4
5
/
16" (11.0cm)
7
1
/
8" (18.1cm)