Installation Guide
8 Installation instructions Kelvinator Air Conditioning
Rooftop installation
If the outdoor unit is installed on a roof structure, be sure to level 
the unit.
Ensure the roof structure and anchoring method are adequate for 
the unit location.
If the outdoor unit is installed on roof structures or external walls, 
this may result in excessive noise and vibration, and may also be 
classed as non-serviceable installation.
caution
•   The outdoor unit is charged with the refrigerant for standard 
pipe length of 7.5m. 
•   When the connecting pipe length is longer than the standard 
length, additional refrigerant should be added into the unit 
according to the above table through the service port on 
3-way service valve on the outdoor unit.
•   Please maintain the shortest distance (3 to 5 metres) and 
shortest misalignment possible between the indoor and 
outdoor units.
•   The maximum allowance length and height is based  
on reliability. Exceeding the maximum may cause poor 
performance or malfunction. 
•   When the level difference between indoor and outdoor units 
is greater than the maximum height of 10 metres, or when 
the outdoor unit is installed above the indoor unit, an oil trap 
should be installed every 5-7 metres.
Pipe Length Elevation and Additional Quantity of Gas
Model Number Suction Pipe Diameter
Discharge Pipe  
Diameter
Standard 
Length (m)
Maximum 
Length (m)
Maximum 
Height (m)
Additional 
Refrigerant (g/m)
KSV26HRE Ø6.35 mm (1/4”) Ø9.52 mm (3/8”) 7.5 15 10 16
KSV35HRE Ø6.35 mm (1/4”)  Ø9.52 mm (3/8”) 7.5 20  10  16
KSV53HRE  Ø6.35 mm (1/4”)  Ø12.70 mm (1/2”)  7.5 25  10  16
KSV62HRE Ø6.35 mm (1/4”)  Ø15.88mm (5/8”)  7. 5  25  10  40
KSV70HRE Ø6.35 mm (1/4”)  Ø15.88mm (5/8”)  7. 5 25  10  40
KSV80HRE  Ø6.35 mm (1/4”)  Ø15.88mm (5/8”)  7. 5 30  10  40
KSV26CRE Ø6.35 mm (1/4”)  Ø9.52 mm (3/8”)  7.5 15  10  12
KSV35CRE Ø6.35 mm (1/4”)  Ø9.52 mm (3/8”)  7.5 20  10  12
KSV70CRE Ø6.35 mm (1/4”)  Ø15.88mm (5/8”)  7.5 15  10  12
maximum length
maximum length
oil trap
maximum height
maximum height
piping length under 7.5m
piping length 7.5m or more
A
A
B
B
indoor unit
indoor unit
outdoor unit
outdoor unit