Installation Guide

14
Existing Installations
When an existing furnace is removed from a vent system
serving other appliances, the existing vent system may
not be sized properly to vent the remaining appliances
(For example: water heater). An improperly sized venting
system can result in the formation of condensate, leakage,
or spillage. The existing vent system should be checked
to make sure it is in compliance with NFGC and must be
brought into compliance before installing the furnace.
NOTE: If replacing an existing furnace, it is possible you
will encounter an existing plastic venting system that is
subject to a Consumer Product Safety Commission recall.
The pipes involved in the recall are High Temperature
Plastic Vent (HTPV). Ifyourventingsystemcontains
thesepipes DONOTreusethisventingsystem! This
recall does not apply to other plastic vent pipes, such
as white PVC or CPVC. Check for details on the CPSC
website or call their toll-free number (800) 758-3688.
CondensateDisposal
The method for disposing of condensate varies according
to local codes. Consult your local code or authority having
jurisdiction. Neutralizer kit P/N 902377 is available for
use with this furnace. Pleasefollowtheinstructions
providedwiththekit.
This furnace has multiple options for positioning the
vent pipe as described in the section, Vent and Inducer
Assembly Options. Each of the condensate drain lines
must be J-trapped using field supplied parts. After the
condensate lines are J-trapped, they may be combined
together when routed to the drain.
CIRCULATING AIR REQUIREMENTS
WARNING:
Donotallowcombustionproductstoenterthe
circulating air supply. Failure to prevent the
circulation of combustion products into the
livingspacecancreatepotentiallyhazardous
conditions including carbon monoxide
poisoningthatcouldresultinpersonalinjury
ordeath.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in conned spaces, all return
ductwork must be adequately sealed. When
returnairisprovidedthroughthebottomofthe
furnace,thejointbetweenthefurnaceandthe
returnairplenummustbeairtight.
Thesurfacethatthefurnaceismountedonmust
providesoundphysicalsupportofthefurnace
withnogaps,cracksorsaggingbetweenthe
furnaceandtheoororplatform.
Returnair andcirculatingairductworkmust
notbeconnectedtoanyotherheatproducing
devicesuchasareplaceinsert,stove,etc.This
mayresultinre,explosion,carbonmonoxide
poisoning,personalinjury,orpropertydamage.
Plenums&AirDucts
• Plenumsandairductsmustbeinstalledinaccordance
with the Standard for the Installation of Air Conditioning
and Ventilating Systems (NFPA No. 90A) or the
Standard for the Installation of Warm Air Heating and
Air Conditioning Systems (NFPA No. 90B).
• Tables 6 - 9 (pages 35 - 38) contain the maximum
airflow and temperature rise data for each furnace input
rate. If the maximum airflow is 1,600 CFM or more, it is
recommended that two openings be used for return air
on upflow furnaces. Downflow furnaces can only use
one return opening.
• It is recommended that the outlet duct contain a
removable access panel. The opening should be
accessible when the furnace is installed in service and
shall be of a size that smoke or reflected light may be
observed inside the casing to indicate the presence of
leaks in the heat exchanger. The cover for the opening
shall be attached in a way that prevent leaks.
• Ifoutside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system
must be designed so that the return air is not less than
60° F (15° C) during operation. If a combination of indoor
and outdoor air is used, the ducts and damper system
Winter Design
Temperature
MaximumFluePipeLength(FEET)
inUnconditioned&ExteriorSpaces
WithoutInsulation WithInsulation*
20 45 70
0 20 70
-20 10 60
*NOTE: Insulation thickness greater than 3/8 inch, based on an
R value of 3.5 (ft x F x hr) / (BTU x in.)
Table2.VentProtection