Installation Guide
4
Connecting Refrigerant Tubing Between 
the Indoor & Outdoor Unit
 CAUTION:
When servicing, cover or seal openings to 
minimize the exposure of the refrigerant system 
to air to prevent accumulation of moisture and 
other contaminants.
After outdoor and indoor unit placement has been 
determined, route refrigerant tubing between the 
equipment in accordance with sound installation practices.
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be flowing through the 
joints during brazing. This will prevent internal oxidation 
and scaling from occurring.
• Refrigeranttubingshouldberoutedinamannerthat
minimizes the length of tubing and the number of bends 
in the tubing.
• Refrigeranttubingshouldbesupportedinamanner
that the tubing will not vibrate or abrade during system 
operation.
• Tubingshouldbekeptcleanofforeigndebrisduring
installation.
• Everyeffortshouldbemadebytheinstallertoensure
that the field installed refrigerant containing components 
of the system have been installed in accordance with 
these instructions and sound installation practices to 
insure reliable system operation and longevity.
• The maximum recommended interconnecting
refrigerant line length is 75 feet, and the vertical elevation 
difference between the indoor and outdoor sections 
should not exceed 20 feet.
• If precise forming of refrigerant lines is required, a
copper tubing bender is recommended. Avoid sharp 
bends and contact of the refrigerant lines with metal 
surfaces.
• A lter dryer is provided with the unit and must be
installed in the liquid line of the system. If the installation 
replaces a system with a filter dryer already present 
in the liquid line, the filter dryer must be replaced with 
the one supplied with the unit. The filter dryer must be 
installed in strict accordance with the manufacturer’s 
installation instructions.
• Optionalequipmentsuchasliquidlinesolenoidvalves,
low ambient, etc., should be installed in strict accordance 
with the manufacturer’s installation instructions.
Outdoor Orifice Removal & Installation
The orifice installed in the outdoor unit has been sized 
for use with the most popularly matched indoor units.  
Depending on the indoor coil that the unit is being matched 
with, the outdoor restrictor may need to be changed. Please 
refer to the Quick Reference Data sheet that is supplied 
with the outdoor unit for more information.
If the outdoor unit has the liquid valve shown in Figure 
2, then the restrictor is located inside the swivel nut 
connection of the liquid valve and not inside the outdoor 
unit’s distributor. Perform steps 1 - 5 if the outdoor restrictor 
needs to be changed.
 CAUTION:
When servicing, cover or seal openings to 
minimize the exposure of the refrigerant system 
to air to prevent accumulation of moisture and 
other contaminants.
 CAUTION:
To prevent damage to the unit or internal 
components, it is recommended that two 
wrenches be used when loosening or tightening 
nuts. Do not over tighten!
1. Using two wrenches loosen the nut and liquid valve.  
Turn the assembly nut counter-clockwise until the orifice 
body halves are separated.
Liquid
Valve
Restrictor
Swivel Nut
Figure 2. LiquidValve,Restrictor,& 
Swivel Nut Adapter
Figure 3. Removal of Orifice










