Installation Guide
18
ApplicationNotes&HeatModeVericationTables(HeatModeOnly)
• ReadallnotesandwarningsfortheCooling-mode
charging charts prior to using these Heating-mode 
charge verification charts. Always use safe and 
environmentally sound methods when handling 
refrigerant handling or servicing the unit. Review 
the factory literature and safety warnings prior to 
servicing.
• Whenrepairingsystemleaks,alwaysuseanitrogen
(inert) gas to protect the refrigerant system and pressure 
check the repair before re-charging. Always replace 
the filter-dryers when performing any repair to the 
refrigeration system with one capable of acid removal. 
After completing the repairs, evacuate the system to 
350 - 500 microns and weigh in the refrigerant to the 
amount specified on the unit rating label.
• Before using the heat mode verification tables,
determine the outdoor ambient temperature and the 
return air temperature to the unit. Locate the appropriate 
location on the units verification chart based on those 
measurements to determine the ideal discharge 
pressure and temperature. See Table 12 (page 19), 
Table 13 (page 19),  Table 14 (page 19),  Table 15 
(page 19),  Table 16 (page 20), Table 17 (page 
20), & Table 18 (page 20). Verify the outdoor fan 
and compressor are running and the outdoor coil is 
free from frost accumulation. Also verify the system 
is not operating in defrost mode before inspecting the 
system.
• Alwaysusequalityinstrumentsthatareingoodworking
order to measure the actual operating point of the 
refrigeration system. The discharge temperature should 
be within 2 degrees of the ideal value and the pressure 
should be within 2%.
• Themostreliablewayofverifyingthesystemisatthe
correct charge is to evacuate the system and weigh 
in the charge to the amount shown on the rating label. 
However, if an inspection with these verification charts 
does not line up with the values shown and the ambient 
temperature is above 50˚ F, then a more accurate 
way to inspect the system for proper charge is with 
the cooling mode charging charts. Switch the unit into 
cooling mode and allow it to operate and stabilize for 
a few minutes then inspect the unit operation with the 
cooling mode charts and procedures.
  Before changing the unit charge, always inspect 
the following items first:
1. Inspect the liquid line temperature on the inlet and outlet 
of the filter dryers. If it is the factory dryer and in good 
condition there should be no temperature difference. 
If the temperature difference is larger than 5˚, replace 
the filter dryer with one that is bi-directional and has 
acid removal capability. Refer to the unit RPL for the 
recommended part number and size.
2. Inspect the units input voltage. Units operating at less 
than 95% of the nominal voltage may deviate more from 
the chart then previously stated.
3. Inspect the input voltage for a phase imbalance. Units 
with greater then a 2% disparity will not operate at the 
rated performance.
4. Verify that the unit filters are installed and are clean. 
The pressure drop across the filters should not exceed 
0.08 in-W.C.
5. Inspect the indoor coil, indoor blower and blower motor 
for cleanliness, clogging, and proper operation.
6. Inspect the system for leaks. If any leaks are detected, 
repair them immediately. Re-inspect the return air and 
ambient temperatures and verify that the correct system 
point on the verification chart was selected.
DO NOT use the charts in systems that have the fan cycling 
under a low-ambient control. Low-ambient controls are 
for cooling operation. In heating mode, the low ambient 
control should be disabled. Unless the unit is in defrost 
mode, the outdoor fan should always operate in conjunction 
with the compressor.
IMPORTANT NOTE:
If the unit is equipped with a liquid valve with an 
outdoor restrictor as shown in Figure 2 (page 4), 
then it is not possible to measure the liquid pressure. 
To approximate the liquid pressure, subtract 7 psig 
from the discharge pressure.
 Shaded boxes indicate flooded conditions.
 Rated design values. The suction pressure will vary from design value if outdoor air flow, entering dry 
bulb, or entering wet bulb temperatures vary.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.










