Installation Guide
7
on the outdoor unit data label. Any other wiring methods 
must be acceptable to authority having jurisdiction.
• Theoutdoorunitrequiresbothpowerandcontrolcircuit
electrical connections. Refer to the wiring diagram / 
schematic for identification and location of outdoor unit 
field wiring interfaces (Figure 12, page 18). Make all 
electrical connections in accordance with all applicable 
codes and ordinances.
• Overcurrentprotectionmustbeprovidedatthebranch
circuit distribution panel and sized as shown on the unit 
rating label and according to applicable local codes. 
See the unit rating plate for minimum circuit ampacity 
and maximum overcurrent protection limits.
• Providepowersupplyfortheunitinaccordancewiththe
unit wiring diagram, and the unit rating plate. Connect 
the line-voltage leads to the terminals on the contactor 
inside the control compartment.
• Useonlycopperwireforthelinevoltagepowersupply
to this unit as listed in Table 1 (page 6). Use proper 
code agency listed conduit and a conduit connector 
for connecting the supply wires to the unit. Use of rain 
tight conduit is recommended.
• 208/230Voltunitsareshippedfromthefactorywired
for 230 volt operation. For 208V operation, remove the 
lead from the transformer terminal marked 240V and 
connect it to the terminal marked 208V.
• Optionalequipmentrequiringconnectiontothepower
or control circuits must be wired in strict accordance 
of the NEC (ANSI/NFPA 70), applicable local codes, 
and the instructions provided with the equipment.
Grounding
 WARNING:
The unit cabinet must have an uninterrupted or 
unbroken electrical ground to minimize personal 
injury if an electrical fault should occur. Do not 
use gas piping as an electrical ground
!
This unit must be electrically grounded in accordance 
with local codes or, in the absence of local codes, with 
the National Electrical Code (ANSI/NFPA 70) or the CSA 
C22.1 Electrical Code. Use the grounding lug provided in 
the control box for grounding the unit.
Table 2. Thermostat Wire Gauge
Thermostat 
Wire Gauge
Recommended T-Stat Wire 
Unit to T-Stat (Length in FT)
2-Wire 
(Heating)
5-Wire 
(Heating/Cooling)
24 55 25
22 90 45
20 140 70
18 225 110
Thermostat Connections
• Thermostatconnectionsshouldbemadeinaccordance
with the instructions supplied with the thermostat and 
the indoor equipment.
• Theoutdoorunitisdesignedtooperatefroma24VAC
Class II control circuit. The control circuit wiring must 
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having 
jurisdiction.
• Thelowvoltagewiresmustbeproperlyconnectedto
the units low voltage terminal block. Recommended 
wire gauge and wire lengths for typical thermostat 
connections are listed in Table 2.
• The thermostat should be mounted about 5 feet 
above the floor on an inside wall. DO NOT install the 
thermostat on an outside wall or any other location 
where its operation may be adversely affected by radiant 
heat from fireplaces, sunlight, or lighting fixtures, and 
convective heat from warm air registers or electrical 
appliances. Refer to the thermostat manufacturer’s 
instruction sheet for detailed mounting and installation 
information.
Positive Temperature Coefficient Resistor (PTCR)
(Select models only)
The PTCR is factory installed and located on the control 
panel of the outdoor unit.This soft start device is for use 
with reciprocating compressors. If a hard start kit is needed 
on this unit, the soft start (PTCR) must be removed first.
START UP & ADJUSTMENTS
Pre-Start Check List
√  Verify the indoor unit is level and allows proper 
condensate drainage.
√  Verify the outdoor coil and top of the unit are free from 
obstructions and debris, and all equipment access/
control panels are in place.
√  Verify air filters are cleaned and properly installed.
√  Verify duct work is sealed to prevent air leakage. 
√  Verify line voltage power leads are securely connected 
and the unit is properly grounded.
√   Verify low voltage wires are securely connected to the 
correct leads on the low voltage terminal strip.
√  Verify power supply branch circuit overcurrent protection 
is sized properly.
√  Verify the thermostat is wired correctly.
Start-Up Procedures
The thermostat's function mode should be set to OFF and 
the fan mode should be set to AUTO. Close all electrical 
disconnects to energize the system.
Air Circulation - Indoor Blower
1.  Set the thermostat system mode on OFF and the fan 
mode to ON.
2.  Verify the blower runs continuously. Check the air 
delivery at the supply registers and adjust register 
openings for balanced air distribution. If insufficient air 
is detected, examine ductwork for leaks or obstructions.










