Use and Care Guide
4
  NOTE:The holesinthedrainpanextensionshouldbe
pressed over the nibs molded into the drain pan. Which 
pair of holes to use will depend on whether the unit is 
installed horizontalleftor horizontalright.Verify proper
positioning for clearance thru the top of the coil cabinet 
beforeafxing.Thedrainpanextensioncanbeinstalled
and removed after the ductwork has been attached to the 
cased coil.
7.ConnecttherefrigerantlinesasoutlinedintheRefrigerant
Lines Connection section.
8. Seal the enclosure as required to minimize air leakage.
9.Reinstallthecoilaccessdoor.
10.Restoreelectricalpowertothefurnace.
HorizontalRightInstallations
1. Disconnect all electrical power to the furnace.
2.Removethecoilaccessdoor.
3.Removetheplugandknockoutfromoneofthethreaded
holes in the horizontal drain pan.
 CAUTION:
The knockout must be removed and discarded 
to ensure proper condensate drainage. Failure to 
do so may result in structural damage, premature 
equipment failure, or possible personal injury.
4. Place the horizontal drain pan on the opposite side of the 
coil. NOTE: If unit has 2 sets of knockouts, remove the 
other set of knockouts in the coil spacing plates and insert 
support rod.
5.Installplug(fromhorizontaldrainpan)intheopendrain
holeinthedrainpanatthebottomoftheunit.Thiswill
block bypass air from entering the system.
6. Slide the coil and the horizontal drain pan assembly back 
into the unit.
7.Removethedrainlineknockoutfromthecoilaccessdoor.
Thiswillallowaccesstothehorizontaldrain.
8. Install drain pan extension (if supplied with unit).
  NOTE:The holesinthedrainpanextensionshouldbe
pressed over the nibs molded into the drain pan. Which 
pair of holes to use will depend on whether the unit is 
installed horizontalleftor horizontalright.Verify proper
positioning for clearance thru the top of the coil cabinet 
beforeafxing.Thedrainpanextensioncanbeinstalled
and removed after the ductwork has been attached to the 
cased coil.
9.ConnecttherefrigerantlinesasoutlinedintheRefrigerant
Lines Connection section.
10. Seal the enclosure as required to minimize air leakage.
11.Reinstallthecoilaccessdoor.
12.Restoreelectricalpowertothefurnace.
Downflow Installations
C7 coils may be installed in downflow applications. It is 
required that the furnace and coil cabinets are securely 
mounted together before setting in place. Fossil fuel
applications require the coil to be placed in the supply air 
stream only.
REFRIGERANT LINE CONNECTIONS
IMPORTANT NOTE TO INSTALLER
C7 Coils are not factory charged with refrigerant. It will 
be necessary to evacuate the indoor coil and lineset 
prior to charging. Refer to the outdoor unit installation 
manual for detailed charging instructions.
System Depressurization
1.Removethecap(Figure1) from the end of the liquid line.
2.Verify pressurization by depressing the Schrader valve
on the end of the liquid line. Listen for any escaping gas. 
If there is no pressure, test the coil for leakage.
• Ifleakageisfound,clearlymarkthelocationofthe
leak and return the coil to the distributor for processing.
• Ifnoleaksarefound,thecoilmaybeinstalled.
3. Depress the valve to relieve all pressure from the coil.
4.Removeanddiscardthevalvecoreandvalvecoreholder
on the liquid line.
5.Removetherubberplugfromthesuctionline.
Installing the TXV
(For Optional Bulkhead Mounted TXV’s)
1.InstalltheTXVretainingnutontotheinletendoftheTXV.
See Figure6(page8).
2.AddsmallamountofHVACapprovedthreadlocktothe
inletendoftheTXV.
3. Install the liquid line and accessory retaining nut onto the 
endoftheTXV.Forliquidlinekitnumbers,seeTable2,
(page 5).
 CAUTION:
To prevent damage to the unit or internal 
components, it is recommended that two wrenches 
be used when loosening or tightening nuts. Do not 
over tighten!
4.AligntheretainingnutontheTXVbodyandhandtighten
both components. Mark a line on both bodies and then 
tighten an additional ¼ turn using two wrenches. See 
Figure 2 (page 5).  NOTE: The movement of the two
lines will show how much the nut is tightened. If a torque 
wrenchisused,tightento10-12ftlbsor14-16Nm.
Orifice Removal & Installation
NOTE: Before proceeding,performsteps1-3intheSystem
Depressurization section and confirm that the restrictor 
orifice size meets the requirements outlined in the outdoor 
unitinstallationmanual.Factorysuppliedoricesizesare
Suction 
Line
Liquid 
Line
Cap
Schrader 
Valve
Figure 1. Suction & Liquid Line Locations