Operating Guide

7
01824A 03036A 01824B 03036B 03642B 030C 03648C 048C 060C 042D 048D 060D
NominalCapacity,MinBTUH 18,000 30,000 18,000 30,000 36,000
30,000
36,000
48,000 60,000 42,000 48,000 60,000
NominalCapacity,MaxBTUH 24,000 36,000 24,000 36,000 42,000 48,000
InstalledOriceSize(in.) .048 .061 .055 .067 .071 .061 .067 .077 .083 .071 .077 .083
NominalAirow,Min(CFM) 800 1,000 800 1,000 1,200
1,000
1,200
1,600 2,000 1,400 1,600 2,000
NominalAirow,Max(CFM) 800 1,000 800 1,200 1,400 1,600
W - Width (in.) 141/2 141/2 171/2 171/2 171/2 21 21 21 21 241/2 241/2 241/2
H-Height(in.) 203/4 203/4 203/4 203/4 263/4 263/4 263/4 301/4 301/4 301/4 301/4 301/4
HL-HeightofLiquidLine(in.) 171/2 171/2 171/2 171/2 231/2 231/2 231/2 27 27 27 27 27
HS-HeightofSuctionLine(in.) 151/2 151/2 151/2 151/2 211/2 211/2 211/2 25 25 25 25 25
Connection - Liquid Line 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Connection - Suction Line 3/4 3/4 3/4 3/4 7/8 3/4 7/8 7/8 7/8 7/8 7/8 7/8
HorizontalDrainKit 920265 920265 920265 920265 920266 920266 920266 920267 920267 920267 920267 920267
NOTES:
1. Individualrestrictorsareavailablebypartnumber-PN664***(where***representsthesize).Example:664103isarestrictor0.103indiameter.
2. RefertosalesspecicationsheetsforListed/Certiedcombinationsofequipmentandrequiredaccessories.
3. XinthemodeldescriptiondesignatesfactoryinstalledTXVforR-410arefrigerant.
4. RefertothecurrentAHRIDirectoryforcertiedratingsofsplitsystems.
5. Notrequiredfor“H”horizontalreadycoils.
Table 2A. C7BA Coil Specifications
Figure 5. Coil Dimensions
W
HS
HL
H
5/8
4
17 3/4
20 3/4
FRONT VIEW
TOP VIEW
01824A Horiz. 03036A Horiz. 01824B Horiz. 03036B Horiz.
NominalCapacity,MinBTUH 18,000 30,000 18,000 30,000
NominalCapacity,MaxBTUH 24,000 36,000 24,000 36,000
InstalledOriceSize(in.) .048 .061 .055 .067
NominalAirow,Min(CFM) 800 1,000 800 1,000
NominalAirow,Max(CFM) 800 1,000 800 1,200
W - Width (in.) 141/2 141/2 171/2 171/2
H-Height(in.) 263/4 263/4 263/4 263/4
HL-HeightofLiquidLine(in.) 231/2 231/2 231/2 231/2
HS-HeightofSuctionLine(in.) 211/2 211/2 211/2 211/2
Connection - Liquid Line 3/8 3/8 3/8 3/8
Connection - Suction Line 3/4 3/4 3/4 3/4
HorizontalDrainKit N/A N/A N/A N/A
NOTES:
1. Individualrestrictorsareavailablebypartnumber-PN664***(where***representsthesize).
Example:664103isarestrictor0.103indiameter.
2. RefertosalesspecicationsheetsforListed/Certiedcombinationsofequipmentandrequiredaccessories.
3. XinthemodeldescriptiondesignatesfactoryinstalledTXVforR-410arefrigerant.
4. RefertothecurrentAHRIDirectoryforcertiedratingsofsplitsystems.
5. Notrequiredfor“H”horizontalreadycoils.
Table 2B. C7BA Coil Specifications