User's Manual
SBS-900 Shore Based Radar Systems
Chapter 9: Planned maintenance
KH-1602-2 issue 1: Standard SBS900 Systems Operator & Maintenance Handbook
Page 118 of 240
10-year maintenance: Changing the static inverter in the RDU
Inspection sheet
5 of 6
FR Forward / Reverse
0
0: Forward run
1:Reverse run
2: Forward run (F/R switching
possible)
3: Reverse run (F/R switching
possible)
ACC Acceleration Time
2.0
0.0-3200
dEC Deceleration Time 10.0 0.0-3200
FH Maximum Frequency 50.0 30.0-500.0 (Hz) Set by TYP
UL Upper Limit Frequency 50.0 0.5 - FH (Hz) Set by TYP
LL Lower Limit Frequency
0.0
0.0 - UL (Hz)
uL Base Frequency, (Motor)
50.0
25-500.0 Set by TYP
uLu Base frequency voltage 1
440
50
-
660 (500/600V class)
As required
Pt V/F Control Mode Selection
0
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5: Dynamic energy-saving
(for fans and pumps)
6: PM motor control
ub Torque Boost
5.0
0.0-30.0
tHr
Motor Thermal Protection
Level
34
or
80
The power limit setting depends on the
gearbox in use:
Standard systems: Set to 34% (750W
motor)
Advanced systems: Set to 80% (1.5KW
motor)
0LN
Electronic Thermal Protection
Level
0
Overload Protection OFF
Overload Stall ON
Sr-1 pre-set Speed Frequency 1 11.0 11Hz (10 RPM)
Sr-2 pre-set Speed Frequency 2
22.0
22Hz (20 RPM)
Sr-3 pre-set Speed Frequency 3
44.0
44Hz (40 RPM)
Sr-4 pre-set Speed Frequency 4
0.0
0Hz
Sr-5 pre-set Speed Frequency 5
0.0
0Hz
Sr-6 pre-set Speed Frequency 6 0.0 0Hz
Sr-7 pre-set Speed Frequency 7 0.0 0Hz
F--- Extended Parameter ENT
F109
Analogue / Logic input function
select
2 Contact Input
F111
Assigns F input (Forward) for
an External Stop safety
command which overrides all
software and manual control
settings.
2
Trip stop command from external input
device disabled.
F170 Base Frequency 2
50.0 25.0-500.0 Set by TYP
F300 PWM Carrier Frequency 4.0 2.0 - 16.0
F301 Auto Restart
0
0: Disabled
1: At auto-restart after momentary
stop
2: ST terminal on or off
3: At auto-restart or when turning STCC
on or off
4: At start-up