Users Manual

Product overview
The solid green line represents the working area that is configured as the
effective range. The furthermost point in the working range defines the ef-
fective range of action (comparable to the cable length for corded devices).
The yellow line represents the tolerance range. The radius is 5 m by default
and cannot be configured. Even in the tolerance range, it must be possible
to see into the hazard areas.
3.1.1 Effective range of action
In the effective range, the full range of functions is ensured when there is a
connection. For the handheld device (KeTop T15x WL) this means that the
emergency stop is illuminated and functional and the enabling switch is al-
so functional.
3.1.2 Tolerance range
When someone enters the tolerance range, this is indicated by vibrations in
the handheld device and optical signals. The emergency stop is no longer
continuously illuminated, but rather the light pulsates. The emergency stop
is still functional, however.
When the enabling switch is pressed, the output is deactivated after ap-
prox. 10 sec. The effective range is the only area where enabling can be
ensured by releasing the enabling switch and pressing it again. An enable
button that has not been actuated cannot be activated.
3.1.3 Area of infringement
When someone enters the infringement area (i.e. exits the tolerance
range), this is indicated right away by strong vibrations and optical signals
of the handheld device (KeTop T15x WL). The emergency stop function is
triggered after 1 sec and the illumination of the emergency stop is deac-
tivated on the handheld device. The machine enters a safe state.
If the enabling switch is pressed, this is deactivated immediately when
someone enters the infringement area. An enabling switch that has no
been actuated can no longer be activated.