User Guide

11
C. Timed and Non-Timed Current Limit
Selection (J3) Jumper J3 is factory set
to “TCL” position for timed current limiting
operation. See Figure 17. For non-timed
current limiting operation, set jumper J3
to “NTCL” position.
TCL (Timed Current Limit) When
Jumper J3 is in the “TCL” position, the
control will go into “STOP” after it is in
overload for a predetermined amount of
time (set by the TCL trimpot).
Resetting the Control After TCL – To reset the control after it has gone into TCL, momen-
tarily set the Start/Stop switch to “START” position or disconnect and reconnect the AC line.
If an On/Off AC Line Switch is installed, set it to “OFF” position and then back to “ON” posi-
tion. If the Start switch is jumpered (START and COM terminals connected), the control
must be restarted by disconnecting and reconnecting the AC line.
NTCL (Non-Timed Current Limit) When jumper J3 is set to “NTCL” position, the control
will not go into “STOP” after it is in overload.
Note: TCL trimpot will have no affect when jumper J3 is in “NTCL” position.
D. DC Tach-Generator Voltage Selection (J1 and J4) For a tach-generator wired to TB3,
set jumper J1 to “T” position. See Figure 18. Jumper J4 is factory set to “7V” position for 7
Volt per 1000 RPM tach-generators wired to TB3. For a 50 Volt per 1000 RPM tach-gener-
ator, set jumper J4 to “50V” position.
Note: When using a tach-generator, the IR trimpot should be set fully counterclockwise.
Note: The tach-generator input is designed for 7 Volt or 50 Volt per 1000 RPM tach-gen-
erators used with 1800 RPM motors. For tach-generators other than 7 Volt or 50 Volt per
1000 RPM or for motors other than 1800 RPM, an external 1/2 watt resistor (RT) must be
used. Install R
T in series with the tach-generator as shown in Figure 19, on page 12.
Jumper J4 must be set to “7V” position.
The value of RT in Ω can be calculated using the following formula:
RT = (1.46 x VT x S) - 19,000
Where VT is the tach-generator voltage (in Volts per 1000 RPM) and S is the base speed of
the motor (in RPM).
J3 Set for TCL Mode
(Timed Current Limit)
(Factory Setting)
J3 Set for NTCL Mode
(Non-Timed Current Limit)
TCL NTCL
J3
J3
NTCLTCL
FIGURE 17 CURRENT LIMIT
MODE SELECTION
50V
7V7V
50V
90V
180V
T
J1
J4 J4
90V
J1
180V
T
J1 Set for 90 Volt Motors
(Factory Setting)
J4 Set for 7V per 1000RPM
Tach-Generator Input
(Factory Setting)
J4 Set for 50V per 1000RPM
Tach-Generator Input
J1 Set for
Tach-Generator Input
Jumper J1 Settings Jumper J4 Settings
FIGURE 18 DC TACH-GENERATOR VOLTAGE SELECTION
Suppose you have a 20 Volt per 1000 RPM tach-generator with a 3600 RPM motor:
RT = (1.46 X 20 X 3600) - 19000 = 86120Ω.
Choose the closest 1/2W resistor value, which is 82000Ω (82kΩ) or 91000Ω (91kΩ).
Readjustment of the MAX trimpot may be necessary to achieve the desired maximum
output voltage.
Example: