INSTALLATION AND OPERATION MANUAL SUPPLEMENT
KBPC-225 (PART NOS. 9391 & 9392)
(A42114) – Rev. C – 10/11/2011 Page 2 of 2
RUN RELAY OUTPUT CONTACTS (TB4)
Can be used to turn equipment "on" or "off" as a function of drive status (Off, Stop, Run). The output contacts are available at Terminal Block
TB4. See Table 1 for drive operating conditions and Run Relay Output Contacts status. See Figure 4 for Run Relay Output Contacts ratings.
TABLE 1
DRIVE OPERATING CONDITION AND RUN RELAY OUTPUT CONTACTS STATUS
Drive Operating Condition Description Normally Open (N.O.) Contact Normally Closed (N.C.) Contact
Power Off Main Power Disconnected Open Closed
Run Mode Normal Drive Operation Closed Open
Stop Mode Selected by Operator Open Closed
Trip Drive Tripped Open Closed
FIGURE 4
DRIVE LAYOUT