Installation Manual
62
Function Group 10: Communication Mode (DIDF Option Board Required)
Function
No. Description Range/Code
Factory
Setting
User
Setting
10.00 * Assigned Comm. Station Number 1 – 247 30
10.01–10.03 Reserved — — —
10.04 Communications Watchdog Timer 0000: Disabled 0001: Enabled 0000
10.05 Watchdog Timeout (Seconds) 0.50 – 2.00 0.50
10.06 Reserved — — —
0 0: Stop 1: Run
1 0: Forward 1: Reverse
2 0: N/A 1: Fault Reset
3 0: Local 1: Remote
4 0: N/A 1: Preset Frequency 1
5 0: N/A 1: Preset Frequency 2
6 0: N/A 1: Preset Frequency 3
7 0: N/A 1: Preset Frequency 4
8 0: N/A 1: Preset Frequency 5
9 0: N/A 1: Preset Frequency 6
10 0: N/A 1: Preset Frequency 7
10.07 Operational Command
11 – 15 Reserved — —
0 0: Stop 1: Run
1 0: Forward 1: Reverse
2 0: Normal 1: Fault
3 0: Local 1: Remote
4 0: N/A 1: Preset Frequency 1
5 0: N/A 1: Preset Frequency 2
6 0: N/A 1: Preset Frequency 3
7 0: N/A 1: Preset Frequency 4
8 0: N/A 1: Preset Frequency 5
9 0: N/A 1: Preset Frequency 6
10 0: N/A 1: Preset Frequency 7
10.08 Drive Status
11 – 15 Reserved — —
00 Normal Operation
01 Short Circuit Trip
02 Current Limit
03 Current Limit Trip
04 Undervoltage Trip
05 Recovered Undervoltage Trip
06 Overvoltage Trip
07 Recovered Overvoltage Trip
08 Stop Mode
09 Flash Error
10 External Fault Trip
11 IODF Error
12 Phase Loss Trip
13 – 15 Reserved — —
16 Watch Dog Trip
17 Unknown Error
18 Data Error
19 Key Error
20 Memory Module Error
21 On Board Memory Error
22 Communication Watchdog Trip
23 Keypad Stop
24 Image Revision Error
25 Image Blank Error
26 Image Checksum Error
27 Image HP Code Error
28 Over Temperature Trip
10.09 Drive Status Description
29 Recovered Over Temperature
10.10 ** Communications Error Count — — —
10.11 ** Motor Voltage — — —
10.12 ** Motor Current — — —
10.13 ** Bus Voltage — — —
10.14 ** Motor Frequency — — —
10.15–10.18 Reserved — — —
*Functions which can only be changed while the drive is in the Stop Mode. **Read only.