TABLE 3
ELECTRICAL RATINGS
AC Line Input Output Net Wt.
Model No.
Part
No.
Maximum
Horsepower
(HP (kW))
Volts AC
(50/60 Hz)
Phase (ะค)
Maximum
Current
(Amps AC)
Fuse or
Circuit
Breaker
Rating
(Amps AC)
Maximum
Voltage
(Volts AC)
Maximum
Continuous
Load Current
(RMS Amps/Phase) lbs kg
Case Size
3
KBDF-13 9623 0.5 (0.37) 115 1 9.6 15 230 2.4
KBDF-23 9688 0.5 (0.37) 208/230 1 6 10 230 2.4
KBDF-23F
1
9691 0.5 (0.37) 208/230 1 7 10 230 2.4
115 1 9.6 15
KBDF-23D 9673 0.5 (0.37)
208/230 1 6 10
230 2.4 2.25 1.05
KBDF-23P
2
9694 0.5 (0.37) 208/230 3 3.1 10 230 2.4
KBDF-14 9624 1 (0.75) 115 1 16 20 230 4.0
KBDF-24 9689 1 (0.75) 208/230 1 10 15 230 4.0
KBDF-24F
1
9692 1 (0.75) 208/230 1 10 15 230 4.0
115 1 16 20
KBDF-24D 9674 1 (0.75)
208/230 1 10 15
230 4.0 2.75 1.25
KBDF-24P
2
9695 1 (0.75) 208/230 3 5.2 10 230 4.0
KBDF-16
4
9625 1.5 (1.13) 115 1 22 25 230 5.5
KBDF-27
4
9690 2 (1.5) 208/230 1 17 20 230 6.7
KBDF-27F
1,4
9693 2 (1.5) 208/230 1 17 20 230 6.7
1.5 (1.13) 115 1 22 25 230 5.5
KBDF-27D
4
9675
2 (1.5) 208/230 1 17 20 230 6.7
2.85 1.30
1 17 20 230
KBDF-27P
2,4
9696 2 (1.5) 208/230
3 8.7 15 230
6.7
A
2 (1.5) 208/230 1 17 20 230 6.7
KBDF-29
2,4
9641
3 (2.25) 208/230 3 11.7 15 230 9.0
4.65 2.10
KBDF-42
2,4
9642 1 (0.75) 400/460 3 2.6 5 400/460 2.0 4.50 2.05
KBDF-43
2
2 (1.5) 400/460 3 3.8 5 400/460 3.3 4.50 2.05
KBDF-45
2,4
9643 3 (2.25) 400/460 3 5.3 10 400/460 4.6 4.50 2.05
KBDF-48
2,4
9644 5 (3.75) 400/460 3 11 15 400/460 8.3 4.50 2.05
B
Notes: 1. Models KBDF-23F, 24F, 27F contain a built-in Class A RFI (EMI) AC Line Filter.
2. Models KBDF-23P, 24P, 27P, 29, 42, 43, 45, 48 contain AC Line Phase Loss Protection.
3. See Figures 4 and 5, on pages 18 and 19, for the mechanical specifications. 4. Models