The earth ground system
WARNING:
AN IMPROPERLY GROUNDED READER COULD RESULT IN
ELECTRIC SHOCK. ENSURE A HIGH CURRENT EARTH GROUND
CONNECTION IS ESTABLISHED BEFORE CONNECTING SUPPLY
POWER.
The system integrator supplies the earth ground system for the Reader mains power as per the IEEE 142-2007
standard, particularly; chapter 5: Sensitive Electronic Equipment Grounding; and chapter 3 pertaining to
lightning protection; and all other chapter sections describing bonding applications.
The system integrator is responsible for ensuring that grounding and power conforms to local regulatory and
safety requirements. The recommendations herein are those ensuring bad grounding does not degrade the
reader performance.
In accordance with IEEE 142-2007 all of the following building/site elements (if available) must be bonded
together:
• Metal frame of the building (if effectively grounded)
• Metal underground water pipe
• Ground ring, concrete encased electrode
The Reader ground bar (supplied by the system integrator) is bonded to the above-mentioned elements. If none
of these elements are available on site, only then a grounding electrode is installed as per NEC to which the
Reader ground bar is bonded. The Reader components ground wires are then connected to the ground bar
clamps as shown in Figure 5-1.
Lightning arrestors should be installed on the interfaces where lightning induced surges can occur.