User manual
56 02.2006 TR10A033-A RE
2x
Safety device
Force limit in the
CLOSE direction
Wicket door contact
static current circuit
Force limit in the
OPEN direction
Operator fault
Operator fault
No reference point
Power failure
Photocell was interrupted, not connected
Obstruction in the door area
Wicket door contact interrupted
Obstruction in the door area
Another impulse via an external push-button,
radio receiver, transparent push-button or
circuit board button T - door opens
(opening reference cycle)
Operator not yet taken through learning
process
Operator needs to perform a reference cycle
Check photocell, if necessary replace
Remove obstruction
Check wicket door
Remove obstruction
If may be necessary to delete the
door data. If the problem re-occurs,
replace the operator
Take operator through learning process
Perform an opening reference cycle
Display Error/warning Possible Cause Remedy
DIL A DIL B DIL D Operator functions Options relay functions
ON ON ON
OFF ON
ON OFF
OFF OFF
X
DIL C Door type
ON Up-and-over door
OFF Sectional door X
DIL D Photocell
ON Photocell activated (automatic timed return only possible with photocell)
OFF Photocell not activated (automatic timed return not possible) X
DIL E Stop circuit with self-monitoring
ON Self-monitoring wicket door contact activated. Testing takes place prior to every travel cycle
(operation only possible with a self-monitoring wicket door contact)
OFF Safety device without self-monitoring X
DIL F Door maintenance indication
ON activated, if the maintenance cycle has been exceeded, this is indicated by the operator lighting flashing
several times after each completed travel cycle
OFF not activated, no signal on exceeding the maintenance cycle X
3x
4x
5x
6x
7x
8x
ENGLISH
Automatic timer after hold-open
phase and advance warning
phase
No special function
No special function
No special function
Relay clocks rapidly during advance warning phase and
at normal rate during door travel, continuous contact
during hold-open phase
Relay responds at CLOSE end-of-travel position
(door-closed signal function).
Relay clocks rapidly during advance warning phase and
at normal rate during door travel (warning light function).
Relay as operator lighting
(external lighting function).